D9412GV2/D7412GV2 | Program Entry Guide | 7.0  RADXAXS 
EN | 146 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
D# Auto Door? 
This command unlocks the door 
Default: 
No 
regardless of the armed state. 
 
Selection: 
Yes or No 
Yes 
When the area assigned in D# Entry 
Area #
 is disarmed, the door is in 
the unlocked state. When that area 
is armed, the door returns to the 
locked state. 
 
No 
Door state is not affected by the 
armed state of the area. 
Use this program item to automatically unlock the 
door (latched, shunt, and strike) when the entry area 
is disarmed. The door re-locks upon Master or 
Perimeter Arming the area. 
 
 
The unlocked state cannot be overridden 
manually. 
 
 
D# Fire Unlock? 
Default: 
No 
Selection: 
Yes or No 
Yes 
Relay activates and shunt is applied 
for the door contact automatically 
upon a Fire Alarm. 
No 
Door remains in its current mode 
upon a Fire Alarm. 
Use this program item to activate the relay for the 
door strike and shunt the door zone automatically 
upon a Fire Alarm. This feature overrides a Secure 
Door state, Locked Door state, Auto Door, and an 
Interlock Faulted point. The relay activates for all 
doors with this prompt programmed as Yes when a 
Fire Alarm occurs in any area. Relays that are 
activated by Fire Unlock can be returned to normal 
only through the keypad using the Door Control 
function. 
 
 
Doors that are activated by Fire Unlock 
must be returned to normal using the 
Door Control function on the keypad. 
 
Each fire alarm that is generated causes 
a Door Unlocked – Automatic Event. 
 
 
D# Disarm on Open? 
Default: 
Yes 
Selection: 
Yes or No 
The area disarms only after the door 
is opened for a user with a valid 
disarm level. 
Yes 
The area disarms whether or not the 
door is opened as soon as a user 
with a valid disarm level presents a 
valid token or card. 
No 
Use this program item to determine if the door needs 
to be physically opened before disarming the area 
upon a valid access request. The user initiating the 
access request needs access levels that allow 
disarming with ID. 
D# Card Type 
Default: 
Selection: 
0 to 3 
Card format is 26-bit Wiegand. 
Do not use. Card format is 37-bit 
fidelity.  
This item must be kept to a value of 0 (26 bit 