White Rodgers CAZ-2 Zone Plus Control Panel 설치 설명서

다운로드
페이지 4
CZ-4
MASTER CONTROL PANEL
Power Indicator LED
System Model Indicator LED
Purge Override
Button 
Boot Button
Adjustable Heating Limit
Adjustable Second
Stage Timer
RJ11 Connection
Sensor Terminals
Zone  Terminal Blocks for
Zone Damper Motors and
Zone Thermostats
24 VAC Transformer
Terminals
Re-Settable Fuse
HVAC Equipment Terminals
Zone Calling Indicators
Mode DIP Switches
Mounting Keyholes
Two at Top also
The CZ-4 basic function is zone control. On a call for heating or cool-
ing, the panel will accept the first call from any zone. Upon accepting
this call, the CZ-4 will open the damper(s) to the zone calling, close 
the damper(s) to those areas not calling, activate the needed HVAC 
controls for heating or cooling, whichever is being called and not ac-
cept any calls for the opposite mode.
Any calls for the opposite mode will be locked out until the initial mode
is either satisfied or a period of time has elapsed that is sufficient for
the first mode to satisfy, a maximum of 20 minutes. A Patent Pending
sequence determines the time the unit has been running or needs to
continue to run in order to adequately provide conditioning for each
mode. If a particular mode has already been calling for 20 minutes or 
longer and an opposite call comes in the CZ-4 will immediately drop 
the mode, enter the purge mode in order to dissipate the conditioned 
air into the zones calling before switching over to provide the new 
conditioning call to its zones.
When using the CZ-4 to control two stage heating and/or cooling, the 
second stage is controlled based upon time after the first stage call
from the thermostat. When any zone calls the panel’s built-in timer 
begins and after the set period of time elapses, the CZ-4 will also ac-
tivate the W3 for Heating or Y2 for Cooling. The Second Stage Timer 
is adjustable from 5 to 23 minutes after the first stage calls. Once the
second stage is on, it will continue to run until the first stage is satis-
fied or the limit setting is reached.
Once all zone thermostats are satisfied for heating and cooling, the
CZ-4 can now accept Fan calls allowing Continuous Air Circulation 
(CAC) in those zones where the thermostat’s Fan Switch is set to ON. 
These zone dampers will be Open while the dampers to the zones 
where the Fan Switch is set to AUTO will be CLOSED.
When all zone thermostats are satisfied for both Heating and Cooling
and all Fan switches are set to AUTO position, the HVAC unit will be 
off and all zone dampers will return to a normally open position. Once 
a zone calls for heating, cooling or fan, the dampers to the calling 
zones remain open and dampers to the zones not calling will close.
SET-UP FOR VARIOUS HVAC EQUIPMENT
The CZ-4 is factory set for conventional fossil fuel (oil or gas) single or 
two stage heating and cooling. The panel only needs to be configured
when using with a conventional electric furnace or hydro-air system 
in order to bring the fan on with a call for heat, or when using with a 
heat pump.
Most all of the panel configuration is done by setting the DIP switches
in the lower center of the panel. Below is shown their setting and 
functions.
ON 
OFF 
7
8
1
2
3
4
5
6
1. 
HT PMP EQP – Heat Pump Equipment – This switch changes the
 output of the HVAC Equipment terminals from conventional Heat-
  ing and Cooling to a traditional Heat Pump Output. When OFF, a
  heat call activates the W1 output. When ON, a Heat call activates
  the Y1  output to bring on the compressor.
2. 
FAN IN HEAT – Activates the O output to turn the Fan on with a
  call for Heat. This is used for Heat Pumps, Electric Heat furnaces
  and Hydro-Air Systems. In the OFF position the CZ-4 will not
  activate the Fan in heating unless there is a fan call from one of 
  the zone thermostats.
3. 
STAT O TO W – Switch is placed to ON when using Heat Pump
  thermostats that use an O terminal to activate the reversing valve
  in COOLING. The O on the thermostat is wired to W on the zone
  terminal in order to determine if the call is for heating or cooling.
  All zone thermostats must operate and be wired the same way.
4. 
STAT B TO W – Switch is used when using Heat Pump thermostats  
  that use a B terminal to activate the reversing valve in HEATING.  
  The B terminal on the thermostat is wired to W on the zone terminal  
  in order to determine if the call is for heating or cooling. All zone  
  thermostats must operate and be wired the same way.
www.white-rodgers.com
244
TECHNICAL
 HELP