TROUBLESHOOTING
Reset Operation 
If a voltage spike or static discharge blanks out the display or 
causes erratic thermostat operation, you can reset the system 
by removing batteries for 2 minutes. After resetting the 
system, replace the batteries. If the system has been reset 
and still does not function correctly perform a power reset.
Note: Be sure to review the installer configuration menu 
settings.
Note: When thermostat is reset, installer configuration menu 
settings and programming will reset to factory settings. 
To reset the programming, clock and configuration 
settings, press 
 and 
 and the SYSTEM touch keys 
simultaneously. The thermostat should go blank and then all 
segments will be displayed momentarily.
Symptom
Possible Cause
Correction Action
No Heat/No Cool/No Fan 
(common problems)
1. Blown fuse or tripped circuit breaker. 
2. Power switch to OFF.    
3. Furnace blower compartment door or 
panel loose or not properly installed.
4. Loose connection to system.
Replace fuse or reset breaker. 
Turn switch to ON. 
Replace door panel in proper position to engage safety 
interlock or door switch. 
Check connections.
No Heat
1. Pilot light not lit. 
2. Furnace Lock-Out Condition. Heat 
  may also be intermittent. 
3. Heat pump system requires service. 
    See fault code table Comfort Alert.
Re-light pilot. 
Many furnaces have safety devices that shut down when 
a lock-out condition occurs. If the heat works intermittently 
contact the furnace manufacturer or local HVAC service 
person for assistance.
No Cool
1. Cooling system requires service. 
    See fault code table Comfort Alert.
 
Heat, Cool or Fan 
Runs Constantly
1. Possible short in wiring. 
2. Possible short in thermostat. 
3. Possible short in heat/cool/fan system. 
4. FAN Switch set to Fan 
ON. 
Check each wire connection to verify they are not shorted 
or touching together. No bare wire should stick out from 
under terminal block. Try resetting the thermostat as 
described above. If the condition persists the manufacturer 
of your system or service person can instruct you on how 
to test the Heat/Cool system for correct operation. If the 
system operates correctly, replace the thermostat.
Thermostat Setting & 
Thermostat Thermometer 
Disagree
1. Thermostat display setting 
  requires adjustment. 
The display can be adjusted +/- 5 degrees. See 
Temperature Display Adjustment in the Configuration Menu 
section.
Furnace (Air Conditioner) 
Cycles Too Fast or Too 
Slow (narrow or wide  
temperature swing)
1. The location of the thermostat and/or 
  the size of the Heating System may 
  be influencing the cycle rate. 
Digital thermostats provide precise control and cycle faster 
than older mechanical models. The system turns on and off 
more frequently but runs for a shorter time so there is no 
increase in energy use. If you would like an increased cycle 
time, choose 
SL for slow cycle in the Configuration menu. 
Comfort Alert™ Fault Codes
Number Displayed in 
7 Segment LED
Comfort Alert Fault
P
Trip
1
Long Run Time
2
System Pressure Trip
3
Short Cycling
4
Locked Rotor
5
Open Circuit
6
Open Start Circuit
7
Open Run Circuit
8
Welded Contactor
9
Low Voltage
System Communication Codes
E
Communication Error
C
For 30 seconds after Communication 
established, then blank