Integrated Furnace Control
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL 
INJURY AND/OR PROPERTY DAMAGE.
 
 DESCRIPTION
INSTALLATION INSTRUCTIONS
The 50A55-3797 is an automatic gas interrupted 
ignition control that employs a microprocessor to 
continually monitor, analyze, and control the proper 
operation of the gas burner, inducer, and fan.
Signals interpreted during continual surveillance of 
the thermostat and flame sensing element initiate 
automatic ignition of the burner, sensing of the flame, 
and system shut-off during normal operation.
These controls incorporate system fault analysis for 
quick gas flow shut-off, coupled with automatic ignition 
retry upon sensing a fault correction. It is designed as a 
replacement for the following controls:
 
 PRECAUTIONS
Installation should be done by a qualified heating and air 
conditioning contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or 
low voltage, have it inspected by a qualified heating and 
air conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical 
codes and ordinances.
This control is a precision instrument, and should be 
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
Following installation or replacement, follow manufacturer’s 
recommended installation/service instructions to ensure 
proper operation.
WARNING
!
Failure to comply with the following warnings could 
result in personal injury or property damage.
FIRE HAZARD
•  Do not exceed the specified voltage.
•  Replace existing control with exact model and
dash number.
•  Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
•  If  the  control  has  been  in  direct  contact  with
water, replace the control.
•  Label  all  wires  before  disconnection  when
servicing  controls.  Wiring  errors  can  cause
improper and dangerous operation.
•  Route and secure wiring away from flame.
SHOCK HAZARD
•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and
line hot wires.
EXPLOSION HAZARD
•  Shut off main gas to appliance until installation
is complete.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-7515B
Replaces 37-7515A
1422
CAUTION
!
Do not short out terminals on gas valve or primary
control. Short or incorrect wiring may damage 
the thermostat.