White Rodgers 36G22-254 36G Series Gas Valve 설치 설명서

다운로드
페이지 8
PART NO. 37-6159G
Replaces 37-6159F
1023
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY 
AND/OR PROPERTY DAMAGE.
Operator: Save these instructions for future use!
The 36G/J22, 36G/J23, 36G/J24 and 36G/J52 combination 
gas valves are designed for direct spark ignition (DSI) and 
hot surface ignition (HSI) system applications. These valves 
are equipped with redundant and main solenoid valves that 
control gas fl ow to the main burners, a pressure regulator 
and a two-position on/off switch for regulation and electrical 
shut-off of the solenoid valves. The 36G/J23, 36G/J24 and 
36G/J52 are also equipped with a slow-opening pressure 
regulator for softer lighting characteristics.
 
 DESCRIPTION
 
 SPECIFICATIONS
Type of Gas:  Natural gas
 
LP gas (use conversion kit)
Pressure Regulator Setting:
Nat. Gas –  2.5 to 5.0" W.C.
LP Gas –  7.0 to 12.0"W.C.
Ambient Temperature:    -40° to 175°F
Pressure Rating: 14" W.C. (1/2 PSI) max.
Voltage:  24 VAC
Frequency:  50/60 Hz
Current:  .360 amps
Mounting Positions:
Multipoise – Control may be mounted in any position.
Parts and Accessories:
F92-0656 - LP to Natural Gas Conversion Kit for use 
on Single Stage 36C, D, E, F, G, H, J valves. Regulation 
range 2.5" to 5.0" W.C.
F92-0659 - Natural to Regulated LP Gas conversion 
Kit for use on Single Stage 36C, D, E, F, G, H, J valves. 
Regulation range 7.0" to 12.0" W.C.
F92-1003 - Adapter Kit for the 36G Gas Valves. Kit in-
cludes: Connector (5/16" to 1/4" hose barb), tube (5/16" 
O.D.) and Hex Wrench (3/32").
36G22, 36G23, 36G24 & 36G52
36J22, 36J23, 36J24 & 36J52
DSI and HSI Single Stage Combination Gas Valve
INSTALLATION INSTRUCTIONS
CONTENTS
Description  ........................................................  1
Specifi cations  ....................................................  1
Precautions  .......................................................  2
Installation  .........................................................  3
 System 
Wiring
Adjustment  ........................................................  4
 
Pressure Regulator Adjustment
Lighting Instructions ...........................................  5
Notes ................................................................... 6
36G
36J
www.white-rodgers.com
www.emersonclimate.com
PIPE SIZES/CAPACITIES
Pipe Sizes 
Available
(inches)
Capacity (BTU/hr) at
1” pressure drop across valve
1/2
" x 
1/2
" NPT 
any combination
140,000
AGA Std. Nat. Gas
(1,000 BTU/cu. ft.)
226,800
LP Gas
(2,500 BTU/cu. ft.)