White Rodgers 24A06G-1 Level Temp Silent Operator For Low Voltage Control Of Electric Heat 카탈로그

다운로드
페이지 1
R
W
Type 24A06 Dual Level Temp
White
Bimetal
Heater #1
Switch #1
Switch #2
Bimetal
Heater #2
Transformer
2-Wire
Heating
Thermostat
Black w/ Red Stripe
Red w/ Black Stripe
L1
Line
L2
L1
Line
L2
Heating
Load #2
Heating
Load #1
Red
Black
Blue
Black w/
White Stripe
Red
Line Voltage
Low Voltage
Line Voltage Field
Low Voltage Field
WIRING
LEVEL-TEMP LOW VOLTAGE
CONTROL SYSTEMS FOR ELECTRIC HEAT
Provides Silent Operation and Narrow Differential Control for Heating 
or Cooling Installations for use with a 2-Wire 24 Volt Thermostat
SPECIFICATIONS
Dimensions Models 24A01 / 05 . . . . . . . .   1
7
/
8
H x 4
1
/
2
W x 2
7
/
16
D
Dimensions Model 24A06. . . . . . . . . . . . .   3
13
/
16
H x 4
13
/
16
W x 2
1
/
8
D
Dimensions Model 24A07. . . . . . . . . . . . .   1
7
/
8
H x 4
9
/
16
W x 1
29
/
32
D
Single Level Temp
Switch Action  . . . . . . . . . . . . . . . . . . . . . .   SPST normally open
Average Time Delay . . . . . . . . . . . . . . . . .   45 seconds
Lead length. . . . . . . . . . . . . . . . . . . . . . . .   18 inches
Ambient temperature range . . . . . . . . . . .   -20 to +140°F
Dual Level Temp
Switch Action  . . . . . . . . . . . . . . . . . . . . . .   Two independent: SPST normally open
Average Time Delay . . . . . . . . . . . . . . . . .   45 seconds
Lead length. . . . . . . . . . . . . . . . . . . . . . . .   18 inches
Ambient temperature range . . . . . . . . . . .   -20 to +120°F
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . .   U.L. listed and C.S.A. approved. Design
   
  complies with U.L. 873 T.I.R.E. standard
   
 
(Temperature Indicating & Regulating Equipment)
FEATURES
• Level-Temp allows low voltage 2-wire thermostat to control line voltage loads such
  as baseboard heaters.
• Conduit hub or screw mounting.
• Ideal for all types of electrical heat.
• Non-critical mounting angle. Universal break-off mounting tabs.
• Dual Level-Temp capable of controlling two separate loads.
24A01G-3
 
Model 
Input 
Thermostat 
A.C. Resistive   A.C. Motor Rating (Inductive)
  Number 
Voltage / Frequency 
Current 
(Non-inductive) 
Full Load 
Locked Rotor
 
24A06G-1 
240 VAC / 60 Hz  0.2A per switch  25A, 6000W, 240v 
12A, 240v 
72A, 240v
DUAL LEVEL TEMPS – Controls Two Independent Loads – Normally Open
  Electrical ratings apply to each switch load
NOTE: Delay approximately 30 seconds opening and 60 seconds closing
REPLACES HONEYWELL R841 SERIES
24A06G-1
Using Two-wire Heating Thermostat to 
Operate Two Separate Heating Loads
ELECTRIC HEAT
PRODUCTS
TECHNICAL HELP
Wiring and Dimension Drawing, 24A01 / 24A05  . . .   page 213
MAKE L1 “HOT”
ON 120V MODELS
NOTE
Use thermostat with a .4A 
fixed heater, or set adjustable 
heater in thermostat at .4 A.
Indicates Canadian Model Number: call 1-800-305-6953 to order
 
Model 
Input 
Thermostat 
A.C. Resistive 
A.C. Motor Rating (Inductive)
  Number 
Voltage / Frequency 
Current 
(Non-inductive) 
Full Load 
Locked Rotor
 
24A01G-3 
240 VAC / 60 Hz 
0.2A 
25A, 6000W, 240v 
12A, 240v 
72A, 240v
 
24A01Z-10 
347 VAC / 60 Hz 
0.2A 
17A, 5900W, 347v 
– 
 
24A05A-1 
120 VAC / 60 Hz 
0.2A 
25A, 3000W, 120v 
16A, 120v 
96A, 120v
 
24A05E-1 
208 VAC / 60 Hz 
0.2A 
22A, 5200W, 208v 
12A, 208v 
72A, 208v
SINGLE LEVEL TEMPS – Normally Open
?
PAGE
213
www.white-rodgers.com
70
HEA
TING