Symptom
Possible Cause
Correction Action
No Heat/No Cool/No Fan 
(common problems)
1. Blown fuse or tripped circuit breaker. 
2. Furnace power switch to OFF.    
3. Furnace blower compartment door or 
panel loose or not properly installed.
4. Loose connection to thermostat or 
system.
Replace fuse or reset breaker. 
Turn switch to ON. 
Replace door panel in proper position to engage safety 
interlock or door switch. 
Tighten connections.
No Heat
1. Pilot light not lit. 
2. Furnace Lock-Out Condition. Heat 
  may also be intermittent. 
 
 
3. Heating system requires service or 
  thermostat requires replacement. 
Re-light pilot. 
Many furnaces have safety devices that shut down when 
a lock-out condition occurs. If the heat works intermittently 
contact the furnace manufacturer or local HVAC service 
person for assistance. 
Diagnostic: Set SYSTEM Switch to HEAT and raise the 
setpoint above room temperature. Within a few seconds 
the thermostat should make a soft click sound. This sound 
usually indicates the thermostat is operating properly. If 
the thermostat does not click, try the reset operation listed 
above. If the thermostat does not click after being reset 
contact your heating and cooling service person or place 
of purchase for a replacement. If the thermostat clicks, 
contact the furnace manufacturer or a HVAC service 
person to verify the heating is operating correctly.
No Cool
1. Cooling system requires service or 
  thermostat requires replacement. 
Same as diagnostic for No Heat condition except set the 
thermostat to COOL and lower the setpoint below the room 
temperature. There may be up to a five minute delay before 
the thermostat clicks in Cooling.
 
Heat, Cool or Fan 
Runs Constantly
1. Possible short in wiring. 
2. Possible short in thermostat. 
3. Possible short in heat/cool/fan system. 
4. FAN Switch set to Fan 
ON. 
Check each wire connection to verify they are not shorted 
or touching together. No bare wire should stick out from 
under terminal block. Try resetting the thermostat as 
described above. If the condition persists the manufacturer 
of your system or service person can instruct you on how 
to test the Heat/Cool system for correct operation. If the 
system operates correctly, replace the thermostat.
Thermostat Setting & 
Thermostat Thermometer 
Disagree
1. Thermostat thermometer setting 
  requires adjustment. 
The thermometer can be adjusted +/- 4 degrees. See 
Temperature Display Adjustment in the Configuration Menu 
section.
Furnace (Air Conditioner) 
Cycles Too Fast or Too 
Slow (narrow or wide  
temperature swing)
1. The location of the thermostat and/or 
  the size of the Heating System may 
  be influencing the cycle rate. 
Digital thermostats provide precise control and cycle faster 
than older mechanical models. The system turns on and off 
more frequently but runs for a shorter time so there is no 
increase in energy use. If you would like an increased cycle 
time, choose 
SL for slow cycle in the Configuration menu, 
step 6 (heat), 7 (cool) or 8 (heat pump). If an acceptable 
cycle rate is not achieved, contact a local HVAC service 
person for additional suggestions.
Forgot Keypad Lockout 
Code
Hold MENU key for 20 seconds and the lockout will reset.
TROUBLESHOOTING
Reset Operation 
Note: When thermostat is reset, installer configuration menu 
settings and programming will reset to factory settings. 
If a voltage spike or static discharge blanks out the display 
or causes erratic thermostat operation, you can reset the 
thermostat by removing the wires from terminals 
and 
(do not short them together) and removing batteries for 2 
minutes. After resetting the thermostat, replace the wires and 
batteries. If the thermostat has been reset and still does not 
function correctly contact your heating/cooling service person 
or place of purchase. 
Note: Be sure to review the installer configuration menu 
settings.
To reset the programming, clock and configuration settings, 
press 
 and 
 and the FAN button simultaneously. The 
thermostat should go blank and then all segments will be 
displayed momentarily.