Part Number 550-101-009/0107

GOLD CGa Gas-Fired Water Boiler — Boiler Manual
Electrical shock hazard — Wherever you see 
TURN OFF POWER
, follow the instructions. Failure to follow 
instructions could result in severe personal injury, death or substantial property damage.
• Reset spill switch, or replace 
rollout switch.
• Boiler is in standby.
• Set thermostat to call for 
heat and recheck 
operation.
• Verify Sequence of 
operationFigure 24
page 37.
Replace control module. 
Retest.
• Boiler water temperature exceeded 
setting on limit switch with thermostat 
calling for heat. Boiler is OK.
• Also check setting on limit switch (should 
be above 140°F.).
• Has it been at least 5 minutes since setting thermostat to 
call for heat? If not, wait 5 minutes. Is system heating?
• Is thermostat set to call for heat? Remove thermostat 
wires at boiler and check continuity across the two wires. 
If circuit isn't closed, check external thermostat (zone 
valve, relay, etc.) wiring. Correct problems and retry. 
• Reconnect external thermostat wiring at boiler.
Is thermostat circuit closed (continuity across wires)?
• If you have sufficient heat — boiler should be in normal 
operating sequence. (See normal sequence of operation, 
Figure 24, page 37.)
• If you have less than sufficient heat —
Is vent or combustion air piping free of blockage?
No
Yes
• Correct conditions and 
recheck operation.
• See Figure 24, page 37 
for normal sequence of 
operation.
Contact your Weil-McLain 
sales representative.
• Replace control 
module.
• Retest.
• Repair/replace 
circulator. Retest.
• Repair/replace 
wiring. Retest.
• Remove CIRCULATOR harness plug from 
CIRCULATOR plug receptacle (
Figure 30,
Item 7, page 53). Check with voltmeter across 
pins of control module receptacle.
Does voltmeter show 120 VAC across pins?
No
Yes
Is boiler System circulator operating?
• Wait 5 minutes.
Is FLAME light on?
No
Yes
• Wait for boiler water to cool to temperature 20 to 30 °F 
lower than temperature set on limit switch.
Are limit switch contacts closed?
Is LIMIT light on?
No
Yes
Are all red lights off?
No
Yes
Wait 30 seconds.
Are all red lights off?
No
Yes
• Replace control module.
• Retest.
• Check limit switch 
contacts with continuity 
checker.
Are limit switch contacts 
closed?
No
Yes
No
Yes
No
Yes
• Replace 
limit switch.
• Retest.
No
Yes
Check spill switch and 
rollout switch continuity —
are switches closed? 
No
Yes
• Check any other 
limit controls wired 
into the limit 
circuit. If all are 
OK, then replace 
control module.
• Retest.
If rollout thermal fuse element or 
spill switch has opened, determine 
cause and correct condition. 
Failure to do so will cause severe 
personal injury, death or 
substantial property damage.
CHART 7 — Spark-ignited pilot — Insufficient heat or no heat (POWER light on steady)
Troubleshooting — spark-pilot boilers 
(continued)
 
11c