WM  550-141-996/1105 
  
 
 
RWB 6104WMNX R1005
Verify that burner specifi cation number (on burner carton) and confi guration agrees with information below.
Table 1. Burner Confi gurations
The table below provides burner specifi cations and starting air settings for NX burners applied to Weil-McLain Model 
UO boilers. Follow all instructions in this burner manual, the boiler manual and the fuel pump literature to install, setup 
and service the burner. 
Boiler 
Model
Burner 
Spec
Firing 
Rate 
(GPH)
Air Tube 
Combina-
tion
Inser-
tion
Primary 
Nozzle
Alternate 
Nozzle
Fuel 
Pump 
Pres-
sure 
(psig)
Head/
Air 
Adjust-
ment 
Plate 
Setting
UO-3 CV
WL5703 
(See Note1)
0.80
NX70LC
1-3/4”
0.65 X 60
o
Delavan
0.65 X 70
o
Hago
150
1.75
UO-3 CV
WL5703
1.00
NX70LC
1-3/4”
0.75 X 60
o
Hago
0.75 X 60
o
Delavan
175
2.50
UO-4 CV
WL5704
1.20
NX90LB
3-1/2”
1.00 X 70
o
Hago
1.00 X 70
o
Delavan
140
4.00
UO-5 CV
WL5705
1.40
NX90LD
3-1/2”
1.10 X 70
o
Hago
1.10 X 70
o
Delavan
160
1.50
UO-3 DV
WL5803 
(See Note1)
0.80
NX70LC
1-3/4”
0.65 X 60
o
Delavan
0.65 X 70
o
Hago
150
1.75
UO-3 DV
WL5803 
1.00
NX70LC
1-3/4”
0.75 X 60
o
Hago
0.75 X 60
o
Delavan
175
2.50
UO-4 DV
WL5804
1.20
NX90LB
3-1/2”
1.00 X 70
o
Hago
1.00 X 70
o
Delavan
140
4.00
UO-5  DV
WL5805
1.40
NX90LD
3-1/2”              1.10  X  70
o
Hago
1.10 X 70
o
Delavan
160
1.50
                                                                          
 
 
1) Shipped as 1.0 GPH Burner Confi guration. The 0.80 GPH input uses same burner as 1.0 GPH input. Replace 
nozzle, adjust pump pressure and Head/Air setting as shown above and install 14”x16” blanket on combustion 
chamber fl oor. (See Maintenance Section for Nozzle Replacement details.)
NX Burner Specifi cations for Weil-McLain Ultra Oil Boilers
NOTICE
The remainder of this manual contains Information to be used ONLY by a 
qualifi ed Service Technician.
Weil-McLain Burner Specifi cations