4.4 
Setpoints and sequence 
 
In single-duct changeover applications the Comfort setpoints for heating and 
cooling sequence are the same (w).  
In applications with electrical heater, radiator or heating / cooling coil the Comfort 
setpoint is at the heating sequence.  
The start of the cooling sequence is linked to “Dead-zone” above the Comfort 
setpoint. The dead zone can be set via parameter P33. 
The setpoints for Energy Saving and Protection mode are below the Comfort 
setpoints (heating) and above the Comfort setpoints (cooling). 
They can be set via parameters P11, P12 (Energy Saving) and P65, P66 
(Protection). 
The control signal for air flow can be limited via parameters P63 and P64.  
See section 4.8.1.  
To simplify the diagram below, only minimum limitation is shown.  
 
w
31
81D
127
T[°C]
w
HeatProt
w
CoolProt
w
HeatEco
w
CoolEco
 
 
 
Comfort mode 
Energy Saving / Protection mode 
Application 
Heating mode 
Cooling mode 
Heating mode 
Cooling mode 
Single duct 
 
 
 
 
Single duct 
with min/max 
limitation 
 
 
 
 
 
 
 
Comfort mode 
Energy Saving  
Protection mode 
Application 
 
 
 
Single duct 
with 
electrical 
heater 
 
 
 
Single duct 
with radiator 
 
 
 
 
 
 
YR 
W
HeatProt
W
CoolProt
 
YR 
W
HeatEco
W
CoolEco
YR 
W
HeatProt
W
CoolProt
 
YE 
W
HeatEco
W
CoolEco
YE 
YE 
W
CoolProt
W
CoolEco
W
HeatProt
W
HeatEco
 
W
HeatProt
W
HeatEco
 
W
W
CoolProt
W
CoolEco
W