RDG100…/RDG110…/RDG140.../RDG160…  Basic Documentation 
CE1P3182en 
Building Technologies 
Functions 
28 May 2009 
4.6 
Additional features 
 
 
The output signals DC 0…10V can be inverted by means of DIP switch 4  
(see section 4.7.3). 
 
 
To ensure a minimum or maximum supply air volume, the output signal for the air 
flow (DC 0...10V or 3-position) can be limited to a minimum value via parameter 
P63 and to a maximum value via parameter P64.  
Both values can be set between 0% and 100%. 
 
T Room 
temperature 
Y10 Control 
output 
Room temperature setpoint 
XpH 
Proportional band Heating 
XpC 
Proportional band Cooling 
Vmin 
Minimum limitation air flow 
max
mi
n
Changeover
XpH
Y10
0%
100%
TR [°C]
XpC
W
C
H
Vmin
Vmax
 
Vmax 
Maximum limitation air flow 
 
If Vmin is not set >0, then a minimum air flow of Vmin is assured in Comfort and 
Energy Saving modes. In Protected mode, Vmin is 0. 
 
Comfort or Energy Saving mode with Vmin 
Protection mode (Vmin = 0) 
max
mi
n
Y
0%
100%
TR [°C]
YV
C
H
Vmin
Vmax
SpH
Comf/Eco
SpC
Comf/Eco
 
ma
x
mi
n
Y
0%
100%
TR [°C]
YV
C
H
Vmin
Vmax
SpH
Prot
SpC
Prot
 
 
 
The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) 
is used to change over from heating to cooling mode and vice-versa. When the 
water temperature is above 28 °C (parameter P37), the thermostat changes over to 
heating mode, and to cooling mode when below 16 °C (parameter P36).  
If the water temperature is between the 2 changeover points immediately after 
power-up, the thermostat starts in heating mode.  
The water temperature is acquired at 30-second intervals and the operating state is 
updated accordingly. 
 
 
16
M
T
w
[°C]
28
 
 
M Operating 
mode 
  Cooling mode 
T
w
 Water 
temperature 
  Heating mode 
 
 
The QAH11.1 cable temperature sensor for automatic heating/cooling changeover 
can be replaced by an external switch for manual, remote changeover: 
Output signal inversion 
Min / Max air flow   
Automatic H/C 
changeover 
Remote heating/ 
cooling changeover