Siemens RDG400 사용자 설명서

다운로드
페이지 42
 
17 / 42 
Siemens 
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation 
CE1P3182en 
Building Technologies 
Functions 
28 May 2009 
4.7 
Control sequences  
4.7.1 
Applications and sequences 
 
 
Application VAV 
Sequences 
Single duct 
h (  \  ), c (  /  ) 
Single duct & electrical heater 
el.h + c (  

\  /  ) 
Single duct & radiator 
rad + c (  r\  /  ),  
Single duct with heat/cool coil 
h + c (  \  /  ) 
 
 
4.7.2 
Sequences overview (setting via parameter P01) 
 
The sequence can be set via parameter P01, if available. 
The thermostats can be used in systems featuring: 
•  Heating only mode (P01=0) 
•  Cooling only mode (P01=1) 
•  Manual heating/cooling changeover (P01=2) 
•  Automatic heating/cooling changeover (P01=3) 
•  Heating and cooling mode (e.g. 4-pipe system) (P01=4) 
 
The available modes depend on the application  
(selected via DIP switch, see section 4.5). 
Parameter 
P01 = 0 
P01 = 1 
P01 = 2 
P01 = 3 
 
Sequence 
T °C
T °C
T °C
 
T °C
T
Mode 
 
 
Available for: 
    
 
Heating mode  
Cooling mode 
Manually select 
heating or 
cooling mode 
 
Automatic 
heating/cooling 
changeover via 
external water 
temperature 
sensor or 
remote switch  
Single duct 
 
 
 
1)
 
 
1)
 
Single duct & 
electrical heater 
3) 3) 3) 3) 
Single duct & 
radiator 
3) 3) 3) 3) 
Single duct with 
heat/cool coil 
 
 
 
2)
 
 
2)
 
 
1) Changeover air 
2)  Changeover water; heat/cool coil 
3)  The controller operates in heating AND cooling mode. P01 is not available 
Notes