Single duct with radiator or floor heating 
 
In single duct applications with radiator or floor heating, the thermostat controls a 
valve plus an auxiliary electrical heater. Parameter P01 is not available. 
The output signal for the air flow can be limited to a minimum and maximum value 
if required (see section 4.6 "additional features"). 
 
The air flow starts to rise when the acquired room temperature is above "setpoint" 
+ "dead zone".  
The radiator receives an ON command when the acquired room temperature drops 
below “setpoint” – “dead zone” (= “setpoint for radiator”). 
 
Note: “Setpoint for radiator” is limited by parameter “Maximum heating setpoint” 
(P10). 
 
The radiator sequence can also be used  for floor heating.  
The "Floor heating limitation function" is described on page 15. 
 
 
ON/OFF radiator / floor heating 
Modulating radiator / floor heating 
 
 
Y
YR
TR [°C]
dz
ma
x
mi
n
Y
0%
100%
TR [°C]
XpC
YV
C
Vmin
Vmax
ON
OFF
W
SDH
 
Y
0%
100%
YR
TR [°C]
XpH
W
dz
ma
x
mi
n
Y
0%
100%
TR [°C]
XpC
YV
C
Vmin
Vmax
 
Y Output 
signal 
TR Room 
temperature 
Effective setpoint Comfort 
H Heating 
sequence 
C Cooling 
sequence 
YV 
Volume flow rate 
YR 
Radiator / floor heating 
XpH 
Proportional band heating 
XpC 
Proportional band cooling 
Vmin  Minimum volume output 
Vmax  Maximum volume output 
 
Note: The diagrams show the PI controller's proportional part only. 
 
 
Setting the sequence and the control outputs 
Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs). 
 
 
Floor heating 
Sequences