Siemens RDG400 사용자 설명서

다운로드
페이지 42
 
29 / 42 
Siemens 
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation 
CE1P3182en 
Building Technologies 
Functions 
28 May 2009 
4.12.1  Parameters Service level 
Pa
ra
m
et
er
Name
Factory setting
Range
RDG
400
Service level
P01
Control sequence 
When 2-pipe / 
2-stage:
1 = Cooling only
When 4-pipe:
4 = H and C
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
P02
User operating mode profile (mode button)
1
1 = (Auto) - Comfort - Protection
2 = (Auto) - Comfort - E Saving - Prot
P04
Selection of °C or °F
0 (°C)
0 = Degrees Celsius (°C)
1 = Degrees Fahrenheit (°F)
P05
Sensor calibration (intern, extern)
0 K
– 3 ... 3 K
P06
Standard temperature display
0
0 = Room Temperature
1 = Setpoint
P07
Display info line 
(2nd line of LCD)
0
0 = --- (No display)
1 = °C and °F 
0..1
P08
Comfort setpoint
21 °C
5 ... 40 °C
P09
Minimum setpoint in Comfort  mode
5 °C
5 ... 40 °C
P10
Maximum setpoint in Comfort mode
35 °C
5 ... 40 °C
P11
Energy Saving heating setpoint
15 °C
OFF, 5 ... WcoolE-saving;
(WcoolE-saving = 40 °C max)
P12
Energy Saving cooling setpoint
30 °C
OFF, WHeatE-saving ... 40 °C; 
(WHeatE-saving = 5 °C min)
P14
Button lock function
0
0 = Unlocked
1 = Auto locked
2 = Manual locked
 
 
 
Parameter display depends on selected application and function 
 
 
 
 
Note