Siemens RDG400 사용자 설명서

다운로드
페이지 42
 
33 / 42 
Siemens 
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation 
CE1P3182en 
Building Technologies 
Handling 
28 May 2009 
5.2 
Operation  
 
See also the operating instructions B3181 enclosed with the thermostat. 
 
Layout 
        
 
 
 
1  Operating mode button / Esc 
 
2  Protection mode and OK 
 
3  Rotary knob for setpoint and parameter adjustment  
 
•  When the thermostat is in normal operation, the actual operating mode and 
status is indicated by symbols. 
•  When a button is pressed, the RDG goes into the Mode selection 
The LCD backlight will turn on, all possible mode selection options (symbols) will 
turn on, indicator element (arrow) will appear on the current mode/status. 
•  When the button is pressed again, the indicator element will toggle to the next 
mode symbol and so on. 
•  After the last press and a timeout of 3 sec, the new selected mode is confirmed, 
the other elements disappear. 
•  After a timeout of 20 sec the LCD backlight will turn off 
 
User action 
Effect, description 
Press left button 
Go into Operating mode selection 
Press left button >3 sec 
Set thermostat to Protection mode  
Remain on left button and  
turn rotary knob clockwise 
Activate temporary timer "Extend presence" 
and set the time (details see page 16) 
Remain on left button and  
turn rotary knob anti-clockwise 
Activate temporary timer " Extend absence" 
and set the time (details see page 16) 
Press left button while "Operating mode 
switch-over" is activated 
Activate " Extend Comfort mode"   
(details see page 16) 
Press right button >3 sec 
Activate/deactivate button lock 
Press right button  
Change to protection mode and back 
Rotate rotary knob 
Adjust the room temperature setpoint  
Press left + right button >3sec, release, 
then press right button >3sec 
Go into parameter mode Service level 
Press left button + right button 3sec, 
release, press left button 3sec, 
then rotate rotary knob counter-clockwise 
min ½ rotation 
Go into parameter mode Expert level, 
diagnostics & test 
 
 
 
Button operation 
2
3