Siemens RDG400 사용자 설명서

다운로드
페이지 42
  
8 / 42 
 
Siemens 
RDG100…/RDG110…/RDG140.../RDG160…  Basic Documentation 
CE1P3182en 
Building Technologies 
Functions 
28 May 2009 
4 Functions 
4.1 
Temperature control 
 
Setting of the control parameters (P01 etc., mentioned throughout the document) is 
described in section 4.12. 
 
The thermostat acquires the room temperature via built-in sensor, external room 
temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), 
and maintains the setpoint by issuing actuator control commands to heating and/or 
cooling equipment. The following control outputs are available: 
•  Modulating PI / P control with DC 0 … 10 V control output 
•  Modulating PI / P control with 3-position control output  
• Modulating PI / P control with PWM output  
•  On/off control (2-position)  
 
The switching differential or proportional band is 2 K for heating and 1 K for cooling 
(adjustable via parameters P30 and P31). 
The integral action time for continuous PI control is 5 minutes (adjustable via 
parameter P35). 
 
The display shows the acquired room temperature or the Comfort setpoint, selecta-
ble via parameter P06. The factory setting displays the current room temperature. 
Use parameter P04 to display the room temperature or setpoint in °F rather than 
°C as needed. 
 
If the thermostat is used in a system with manual heating/cooling changeover 
(P01=2), the heating   and cooling   symbols on the display show the terminal 
unit status. Thus, the symbols are displayed even when the thermostat operates in 
the neutral zone. For all other cases, the heating   and cooling 
 symbols are 
displayed when the heating or cooling output is energized. 
Concurrent display of the current temperature or setpoint in °C and in °F 
(parameter P07) is possible. 
General note 
Display 
 / 
 
Concurrent display of 
°C and °F