MOTOR FULL LOAD AMPS
: 200 AMPS
SERVICE FACTOR
: 1.15 X FLA
OVERLOAD
CLASS:  10
NEMA
DESIGN: B
INSULATION
CLASS: B
LINE VOLTAGE
INPUT:  480 VOLTS 
Range: 50 - 100% of Unit 
MAX CURRENT AMPS
Increments of 1
Range: 1.00 - 1.3
Increments of 0.01
Range: 5 - 30
Increments of 5
Range: A - F
Range: A - S
Range: 208 - 600
LINE FREQUENCY
HZ:  60
Range: 50 or 60
SP.1 Basic Configuration (Setpoint Page 1)
In Setpoint Page 1, the TX is looking for the following basic
nameplate data of the motor.
SP1.1
Motor Full Load Amps: Allows the user to enter the
motor’s FLA rating.  Range of adjustment is 50 - 100%
(less programmed service factor).
SP1.2
Service Factor: Sets the pickup point on the overload
curve as defined by the programmed motor full load
current.  Ex: If the motor FLA is 100 and the service
factor is 1.15, the TX overload pickup point will be 115
Amps.
SP1.3
Overload Class: Choose the motor protection overload
class, range from 5-30.
Ex: Overload Class 10 will trip in 10 seconds at six
times FLA.
SP1.4
NEMA design: The motor design maximum allowed slip (Select from
Class A through F).
SP1.5
Insulation Class: The motor insulation temperature class (Select  A,
B, C, E, F, H, K, N or S).
SP1.6
Line Voltage Inut: Applied system nominal voltage.
SP1.7
Line Frequency: The user may choose either 50 Hz or 60 Hz.