Toshiba Remote Starter ME00070B 사용자 설명서

다운로드
페이지 32
APPLICATION EXAMPLES 
 
26 
ME00070B 
TMS7 SERIES 
Application Examples 
8.1  Installation With Line Contactor 
 
OR
OR
S1
Start Contact
Legend
S2
Reset Pushbutton
F1
Semiconductor  Fuses  (optional)
K1M
K1M
Line Contactor
C24  mo dels
C7
C6
R34
R33
L2B
L3B
L1B
E
T2
G ND
C5
C4
C3
R43
R44
MOTOR
THERMISTOR
R24
R23
L1
L2
L3
T1
T3
A1
A2
A3
R14
R12
R11
C1
C2
3  PHASE
SUPPLY
TO MOTOR
230V
+10
-15
-15
+10
400V
C45  mode ls
575V
+10
-15
-15
+10
460V
F1
K1M
CO NTROL
SUPPLY
I11
I12
I21
I22
  S1
  S2
I33
I34
I43
I44
 
 
Description: 
The TMS7 is applied with a line contactor (AC3 rated). The line 
contactor is controlled by the TMS7 Main Contactor output, 
which by default is assigned to RELAY OUTPUT A (terminals 
R44, R43). 
The control supply must be sourced from before the contactor. 
 
Function Settings: 
Function 21. Relay Output A Functionality = 11 
(Assigns the Main Contactor function to Relay Output A) 
 
8.2  Installation With Bypass Contactor 
 
K1M
OR
O R
S1
Reset Pushbutton
L egend
S2
Stop  Pushbutton
S3
Start Pushbutton
K1M
Bypass Co ntactor
F1
Semi conductor Fuses (optional)
I43
I44
I33
I34
S3
I11
I12
I21
I2 2
 S1
 S2
C 24  mo dels
C7
C6
R34
R33
L2B
L3B
L1B
E
T2
GND
C5
C4
C3
R43
R44
MOTOR
THERMISTOR
R24
R23
L1
L2
L3
T1
T3
A1
A2
A3
R14
R12
R11
C1
C2
3 PHASE
SUPPLY
TO MO TOR
230V
+10
-15
-15
+10
400V
C4 5 mod els
575V
+10
-15
-15
+10
460V
F1
K1M
CONTROL
SUPPLY
 
Description: 
The TMS7 is applied with a bypass contactor (AC1 rated). The 
bypass contactor is controlled by the TMS7 RUN OUTPUT 
(terminals R34, R33). 
 
Function Settings: 
- no special settings required.