Toshiba Remote Starter ME00070B 사용자 설명서

다운로드
페이지 32
TROUBLE SHOOTING 
 
30 
ME00070B 
TMS7 SERIES 
Code 
Description 
TMS7 and reconnect the motor in 6 Wire. 
 
Incorrect main control module. 
The TMS7 is fitted with an incompatible main control 
module. 
1.  Fit a suitable main control module. 
CPU error 
Reset the TMS7. If the problem persists contact your 
supplier. 
 
9.2 Fault History 
 
The TMS7 includes a Fault History Log that records the last 
eight trip events. Each trip is numbered. Trip number 1 is the 
most recent trip with trip number 4 being the oldest. 
1 - 4
Trip Number
1 = Most recent trip
2 = Previous trip
4 = Oldest trip
Trip Code
.
.
.
 
The Fault History can be viewed by selecting Function 101. 
Fault History and using the <UP> and <DOWN> keys to scroll 
through the Fault History. 
CAUTION
 
NOTE: 
The TMS7 records trips in the Fault History log 
immediately after they are detected, this requires 
control voltage to be present after the trip. Trips 
caused by or involving a loss of control voltage 
may not be recorded. 
 
A ‘marker’ can be inserted into the Fault History log to identify 
trips that have occurred after placement of the ‘marker’. To 
insert a ‘marker’ enter the programming mode and move to 
Function 101. Fault History. Then simultaneously depress the 
<UP> and <DOWN> and <STORE> keys. The marker is added 
as the most recent fault and is displayed as three horizontal 
lines as shown below. 
 
 
CAUTION
 
NOTE: 
Trip makers must be separated by at least one trip 
and cannot be placed consecutively. 
 
9.3  General Faults
 
 
Symptom 
Cause 
Uncontrolled start.  Power factor correction capacitors 
connected to the TMS7 output. Remove 
any power factor correction from the output 
of the soft starter. Connection of power 
factor correction capacitors to the output of 
a soft starter can result in damage to the 
SCRs so they should be checked by using 
the SCR test described in section 9.4 Tests 
and Measurements. 
Damaged SCRS. Verify soft starter 
operation using the SCR test described in 
section 9.4 Tests and Measurements. 
Damaged firing circuit. Verify the TMS7 
SCR firing circuit using the Power Circuit 
Test described in section 9.4 Tests and 
Measurements. 
TMS7 will not 
operate. 
Local push buttons not active. The TMS7 
may be in remote control mode. (Refer to 
Function 20. Local/Remote Operation
Remote control inputs not active. The 
TMS7 may be in local control mode. (Refer 
to Function 20. Local/Remote Operation
Faulty start signal. Verify any circuits 
connected to the TMS7 remote control 
inputs. The state of the remote circuits is 
indicated by the TMS7 remote control input 
LEDs. The LEDs are illuminated when there 
is a closed circuit. For there to be a 
successful start there must be a closed 
circuit across the start, stop and reset 
circuits. 
No, or incorrect control voltage. Ensure 
the correct control voltage is applied to the 
inputs A1, A2, A3.  
Restart delay active. The TMS7 cannot be 
started during the restart delay period. The 
period of the restart delay is set using 
Function 31. Restart Delay
Auto-reset function active. If there has 
been a trip and the auto-reset function is 
active the fault must be manually reset 
before a manual restart can be attempted. 
(Refer to Functions 70, 71, 72 & 73 ) 
TMS7 in programming mode. The TMS7 
will not run while in programming mode. 
The motor will not 
accelerate to full 
speed. 
Start current too low. Check the load is 
not jammed. Increase start current using 
Function 2. Current Limit
Function setting 
cannot be made or 
are not recorded. 
Incorrect programming procedure
Function settings must be stored using the 
<STORE> button. Refer to section 7.1 
Programming Procedure for further detail. 
Function settings are locked. Ensure that 
Function 112. Function Lock is set for 
Read/Write.