INSTALLATION 
TMS7 SERIES 
ME00070B 
Installation 
6.1  General Layout Diagrams 
 
TMS7-4007 ~ TMS7-4055 
 
TMS7-4075 ~ TMS7-4132 
 
TMS7-4150 ~ TMS7-4800 
 
 
4.2  Power Termination Configuration 
 
The bus bars on models TMS7-4150 ~ TMS7-4800 can be 
adjusted to provide four different input/output power terminal 
configurations. 
 
Input/Output
Input
Output
Input/Output
Output
Input
 
To adjust the bus bar configuration first remove the TMS7 cover 
and main control module. Next loosen and remove the bus bar 
fixing bolts. The bus bars can then be removed and reinstalled 
into the starter in the desired configuration. The fixing bolts 
should then be refitted and tightened to a torque of 8.5NM. 
 
When re-orienting bus bars L1, L2, L3 the current transformers 
must also be relocated. 
 
Care must be taken to ensure that foreign matter does not 
contaminate the jointing compound and become trapped 
between the bus bar and its mounting plate. If the paste does 
become contaminated, clean and replace with a jointing 
compound suitable for aluminium to aluminium, or aluminium to 
copper joints. 
 
4.3  Mounting Instructions 
 
Models TMS7-4007 ~ 4132 can be wall mounted or installed 
inside another enclosure. These models can be mounted side 
by side with no clearance but a 100mm allowance must be 
made top and bottom for air intake and exhaust. 
100mm Minimum Clearance
100mm Minimum Clearance
100mm Minimum Clearance
100mm Minimum Clearance
100mm Minimum Clearance
100mm Minimum Clearance
 
Models TMS7-4150 ~ 4800 have an IP00 rating and must be 
mounted in another enclosure. These models can be mounted 
side by side with no clearance but a 200mm allowance must be 
made top and bottom for air intake and exhaust. 
200mm Minimum Clearance
200mm Minimum Clearance
200mm Minimum Clearance
200mm Minimum Clearance