Siemens Barcode Reader SIMATIC S7-400 전단

다운로드
페이지 1
SIMATIC Modular Controllers
59
Point-to-point connection
Point-to-point link via communications processors (CPs) is an 
extremely powerful and low-cost alternative to bus systems.
The advantage of point-to-point links over bus systems is es-
pecially pronounced when only a few (RS 485) devices are to 
be connected to the SIMATIC S7.
The CPs can also easily link third-party systems to the 
SIMATIC S7. Thanks to the great flexibility of the CPs, different 
physical transmission media, transmission rates or even cus-
tomized transmission protocols can be implemented.
The CPs have a rugged plastic housing with LEDs for displaying 
operating states and faults.
For each CP there is a configuring package on CD with elec-
tronic manual, parameterization screen forms and standard 
function blocks for communication between the CPU and 
the CP.
The configuration data are stored in a system block and 
backed up in the CPU. When modules are replaced, the new 
module is therefore immediately ready for use.
With the S7-400 point-to-point link modules, adaptation to 
the physical transmission media is achieved by plugging in the 
relevant interface submodules, without the need for external 
converters.
Point-to-point links for SIMATIC S7-400
Scanner 
Barcode 
reader
Process 
controller
SIMOVERT 
SIMOREG
Modem
PC
Printer
Robot 
control
BDE 
terminal
3rd party 
PLC
G_
S
T
7
0
_
X
X
_
0
0
6
8
7
SIMATIC S7
Technical data: Point-to-point connection
Application
High-speed response 
with low data volumes
Interconnection
Low-cost:
With one variable 
interface
High-speed:
With two variable inter-
faces
Transmission rate
High (115 200 bit/s)
Low (38 400 bit/s)
High (115 200 bit/s)
Loadable protocols 
(Order No. group: 6ES7 340-)
MODBUS Master (-1AA.),
MODBUS Slave (-1AB.),  
Data Highway (-1AE.)
Module
CP 440
CP 441-1
CP 441-2
Order No. group: 6ES7
440-1.
441-1.
441-2.
Physical transmission media
RS 232C (V.24)
All transmission methods, all interface modules, 
plug-in, serial
20 mA (TTY)
RS 422/485 (X.27)
 (up to 32 nodes)
Integrated transmission protocols
ASCII
Printer driver
3964 (R)
RK 512