Basic Operation 
Siemens Building Technologies, Inc. 
 
9 
If the room temperature sensor input to the Unit Vent Controller fails or the LTDT equals ON, 
the controller goes through the following shutdown sequence: 
•  Outdoor air damper is closed. 
•  Heating is full ON (except electric, which is OFF). 
•  Cooling is full OFF. 
•  Face-bypass damper is open to face. 
•  Fan is OFF. 
•  Auxiliary radiation is OFF. 
•  Two-position heating valve actuator is open. 
•  Two -position cooling valve actuator is closed. 
NOTE: 
DO 2 is not commanded by the fail-safe mode; all other DOs can be affected. 
If the discharge air temperature sensor fails, the following conditions occur: 
•  If the last valid value is greater than 150 degrees, the heat is turned off, the outdoor 
air damper is closed and the fan is turned on.  
•  If the sensor does not come back within 10 minutes or if the last valid value is less 
than 150 degrees, the controller shuts down. 
If a failed sensor returns or if the LTDT turns off, normal control resumes. 
Analog and digital outputs cannot be commanded when the controller is in fail-safe mode; 
however, failed points may be overridden, allowing the controller to return from fail-safe 
mode. In this instance, room temperature control is not possible.