Hardware and Engineering
12/01 AWB2700-1428GB
16
XC-SYS1 operator module
The operator module always forms the final component of several 
stacked modules, and provides access to the controller.
Task
The operating mode selector switch (OMS) is used to select oper-
ating states MRES, STOP, RUN or RUN-P. The current PLC status is 
indicated by the three LEDs. Parameters such as time and pass-
word, the current PLC states are shown on the display. You can 
use the menu selection switch (MSS) to enter passwords and 
modify specific states. Entry is menu-guided.
Setup
Operating mode selector switch (OMS)
The operating mode selector switch sets thestatus that the PLC 
assumes after the power supply is switched on. If you wish to 
change the switch position with the power supply switched on, the 
PLC will switch to the new status.
You can select one of the four settings. After the power supply 
voltage is switched on, the PLC executes the following function:
Figure 28:
Setup of the operator module
LED STOP
LED RUN
SF LED
Display
Operating mode selector switch (OMS)
Menu switch
Battery
Eject button for CompactFlash card
CompactFlash card
a b c
d
e
f
h
g
i
STOP
RUN
RUN
RUN-P
STOP
MRES
SF
Position
Function
RUN
The user program is processed. A debugging or status 
change initiated from the PC is not possible.
RUN-P
The user program is processed. All access functions are 
available via the programming device.
STOP
The user program is not processed. A program can be 
loaded, started or stopped.
MRES
The simple variables and POU variables and those 
assigned with RETAIN will be initialised.