Burnham Series 3 Power Flame Low NOx 데이터 시트

다운로드
페이지 2
Burner Equipment
Equipment
Fuel
Description
Control Cabinet
Gas, Gas/#2 Oil
NEMA 1A with hinged door
Control Voltage Transformer
Gas, Gas/#2 Oil
Included
Motor Starter
Gas, Gas/#2 Oil
Magnetic starter with overload protection
Fusing
Gas, Gas/#2 Oil
Control circuit only
Ignition
Gas, Gas/#2 Oil
Gas/Electric pilot
Signal Lights
Gas, Gas/#2 Oil
(4) - power on, fuel valve open, call for heat, flame failure
Air Flow Safety Switch
Gas, Gas/#2 Oil
All Models
Gas Train
Gas, Gas/#2 Oil
UL gas train for minimum inlet pressure indicated on Burner 
Information table. Assembled, wired and mounted on unit
consisting of the following:
Manual shut off valve
Gas pressure Regulator
Manual leak test valve
40 & 50: 2 Gas Valves
150 & Larger: 2 Gas Valves
Main Gas Valve: Motorized type
Auxillary gas valve: Solenoid type
60 -125: Single Motorized Gas Valve with Proof of closure 
60 & Larger: High and Low gas pressure switches
Oil Pump
Gas/#2 Oil
Remote oil pump set with motor and accessories mounted on  
boiler skid
Oil Firing Type
Gas/#2 Oil
100 - 250:  Pressure Atomizing
300 and larger:  Air Atomizing
Pilot Gas Controls
Gas, Gas/#2 Oil
All models have gas/electric pilot, manual pilot shut-off valve, pilot 
gas pressure regulator and solenoid gas valve
Fuel Changeover
Gas/#2 Oil
Manual switch
Flue Gas Recirculation
Gas, Gas/#2 Oil
Induced flue gas recirculation, no external fan is required
SERIES LN3 
LN-2