Service
10
Sequence of operation
 
Table 1A_(continued from previous page) Sequence of Operation - Space Heating and DHW
OPERATION
DISPLAY
9.  If the DHW thermostat remains on for more than                   30 
minutes, and the space heating call for heat is also on, then 
the control will turn on the boiler pump, turn off the DHW 
pump after 2 seconds, and resume firing based on the 
space heating set point.  As long as both the space heating 
and DHW calls for heat remain active, the control will switch 
back and forth between the two modes until one of them is 
satisfied.
HTR: RUN STG 12
OUT: 123.0F(129)
10. Once both calls for heat are satisfied, the control will turn 
    off  the  burners.    The  blower  will  remain  on  for  the                          
  30 second postpurge cycle.  Any pumps that are running 
  will continue to run for their respective pump delay times, 
  then turn off.
HTR: POSTPURGE
OUT: 127.4F(129)
11. Boiler pump off, system pump continues its delay if 
 longer.
HTR: Standby
OUT: 124.7F(129)
12. System pump off.
HTR: Standby
OUT: 122.9F(129)
 Copper-fin II/IIE Boiler, Water Heater and Pool 
Service Manual