MODELS  MUA006A • MUA008A
Page 5
INSTALL THE  DAMPER
OUTSIDE AIR
TO CENTRAL SYSTEM
RETURN AIR OR INTERIOR
WALL REGISTER 
DAMPER FLAP (Install in
vertical position shown.)
AIR FLOW
AIR FLOW
SET SCREW
Install the damper as shown. Make sure damper flap is in a verti-
cal position when closed and power is off. The set screw can be 
used to adjust the damper opening - thereby balancing the inside 
and outside air pressure when the range hood exhausts at high 
speed.
PRESSURE SWITCH 
OPERATION
The pressure switch is designed to operate when the static 
pressure increases to 0.05” Ps or more. It may not operate at low 
speeds since the pressure is below this limit.
MULTIPLE DAMPERS
More than one damper may be required to balance the system. 
If more than one is required use (1) MUA006A or MUA008A 
and then use the 54060012 (6”) or 54060013 (8”) dampers as 
additional dampers.
INSTALLATION OF 
PRESSURE SWITCH AND 
PROBE
For the probe & pressure switch to work effectively the roof or 
wall cap must have a spring loaded damper.