Movincool OP24 사양 시트
Office Pro 24
800.367.8675 • www.spot-coolers.com
Copyright © 2004 Spot Coolers, Inc. All rights reserved.
Cooling Capacity
Dimensions
Electrical
Characteristics
Compressor
Characteristics
Fan
Characteristics
Safety Devices
Miscellaneous
Features
Btu/hr. @ 95º
At 60% Relative Humidity
23,300
Width (Inches)
21
Depth (Inches)
27
Height (Inches)
47
Weight (Pounds)
210
Shipping Weight
250
Power Supply (Volts)
208/230 1phase
Power Consumption (Kilowatts)
2.7
Current Consumption (Amperes)
11.2
Fuse Size (Amperes)
20
NEMA Plug Configuration
6-20
Min-max Voltage
195-250 Volt
Power Cord Gauge
12AWG (3 Core)
Power Cord Length (Feet)
6
Compressor Type
Hermetic Rotary
R 22 Charge (Pounds)
2.14
Operating Conditions: Min-max ºF
65º-95ºF, 50% RH
Evaporator:
Fan Type
Centrifugal
Air Flow (CFM) High/Low
630/545
Max. External Static Pressure
0.5
(Inches Of Water Gauge)
Condenser:
Condenser:
Fan Type
Centrifugal
Air Flow (CFM) High/Low
870/760
Max. External Static Pressure
0.16
(Inches Of Water Gauge)
Compressor Overload Relay
Yes
Fan Motor Protection
Yes
Anti-freeze Thermostat
Yes
Automatic Tank Shut-off
Yes
Condensate Tank Capacity (Gallons)
5
High-pressure Switch
Yes
Compressor Short-cycle Protection
Yes
Fan Mode Switch
Yes
Automatic Restart
Yes
Thermostat
Yes
Control Panel
Programmable
Thermostat Control
Electronic
Operating Cost $0.194
Humidity Removed @ 60% RH
1.26
Accommodates Condensate Pump
Yes
Sound Level (Db) High/Low
63/61
Max Evaporator Ducting Length*(Ft.)
50
Max Condenser Ducting Length*(Ft)
45
*subtract 10 Ft. For Every 90º Bend