Amana PTH094G25AXXX 사양 시트
P
roduct
S
PecificationS
SS-DPTAC
www.amana-ptac.com
5
* Actual vent CFM performance will vary due to application and installation conditions.
Notes
Notes
¹ Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
2 Minimum voltage on 115-volt models is 109 volts; maximum is 127 volts.
3 Overcurrent protection for all units without electric heaters is 15 amps.
⁴ R-410A refrigerant used in all systems.
⁵ All units meet or exceed ASHRAE 90.1 standards.
⁶ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
2 Minimum voltage on 115-volt models is 109 volts; maximum is 127 volts.
3 Overcurrent protection for all units without electric heaters is 15 amps.
⁴ R-410A refrigerant used in all systems.
⁵ All units meet or exceed ASHRAE 90.1 standards.
⁶ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Model
5, 6
PTC
072G
00XXX
PTC
092G
00XXX
Voltage 2
115
115
Capacity (BTU/h)
7000
9000
Amps
6.9
8.3
Watts
585
795
EER
11.9
11.3
Min. Circuit Amps 1
,
3
8.3
10.1
CFM (Cool/Wet Coil)
High
290
290
Low
264
264
CFM (Dry Coil)
High
310
310
Low
282
282
Ventilated Air, (Fan Only)*
65*
65*
Dehumidification (Pints/Hr.)
1.7
2.3
Net Weight (lbs.)
98
102
Ship Weight (lbs.)
113
117
(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Configuration)
P
roduCT
s
PeCifiCATions
: PTC / PTH m
odels
— e
leCTriC
H
eAT
P
erformAnCe
P
roduCT
s
PeCifiCATions
: PTC m
odels
— C
ooling
(u
niTs
for
H
ydroniC
H
eATing
)
Voltage
Electric
Heater
Size (kW)
No. of
Stages
Stages
Nominal Heating (BTU/h)
Total
Watts ⁶
Total
Amps
Amps
Min. Circuit
Ampacity²
MOD ⁴
(amps)
Power
Cord
@ 230V
@ 208V
@ 265V
230/208V
2.5
1
8,500
6,800
- -
2,570 / 2,115
11.2 / 10.1
14.1
15
6-15 P
230/208V
3.5
1
12,000
9,900
- -
3,570 / 2,935
15.5 / 14.1
19.5
20
6-20 P
230/208V
5
1
17,100
14,000
- -
5,070 / 4,160
22.1 / 20.0
27.6
30
6-30 P
265V
2.5
1
- -
- -
8,500
2,570
9.7
12.2
15
7-20 P
265V
3.7
1
- -
- -
12,600
3,770
14.2
17.9
20
7-20 P
265V
5
1
- -
- -
17,100
5,070
19.2
23.9
25
7-30 P
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
maximum is 292 volts.
⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be
cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric
heat at approximately 24°F outdoor ambient.
⁶ Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12
⁷ Specify two-digit heater kW size to complete model number.
⁸ R-410A refrigerant used in all systems.
⁹ All units meet or exceed ASHRAE 90.1 standards.
¹⁰ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
⁷ Specify two-digit heater kW size to complete model number.
⁸ R-410A refrigerant used in all systems.
⁹ All units meet or exceed ASHRAE 90.1 standards.
¹⁰ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.