Description of the I/O Modules 
Excel 800 
EN1B-0410GE51 R0908A 
 
24
Analog Output Modules 
Types of Analog Output Modules 
Table 27. Excel 800 Analog Output Modules 
type 
description 
housing 
XF822 
Panel Bus Analog Output 
Module 
light-gray 
XFR822 
Panel Bus Analog Output 
Module with manual overrides 
light-gray 
XFL822 
L
ON
W
ORKS
 Bus Analog Output 
Module 
dark-gray 
XFLR822 
L
ON
W
ORKS
 Bus Analog Output 
Module with manual overrides 
dark-gray 
XS821-22 terminal 
socket 
light-gray 
 
Features 
•  8 analog outputs;  
can also be configured per output as binary outputs  
(0 ─ 10 V, 2 ─ 10 V, ON/OFF, or floating) 
•  Corresponding output status LEDs (red) 
•  XFR822AU/XFLR822AU: 8 manual overrides, see figure 
below 
 
 
Fig. 38. XF822AU Analog Output Module with terminal 
socket 
Legend 
 1  Service button S1 
  2  Hex switch S2 
 3  Manual overrides 
 4  Output LEDs 
 5  Service LED 
 6  Power LED 
Functionality of service LED and power LED: see Table 42 
and following. 
Terminals 
 
Fig. 39. Terminal assignment and internal connections of 
the Analog Output Modules 
Table 28. Description of the Analog Output Module 
terminals 
ter-
minal 
signal 
comment 
71, 75
COM a 
2-wire communication bus 
(LON/Panel Bus) 
72, 76
COM b 
2-wire communication bus 
(LON/Panel Bus) 
73, 77
24 V~ 
Power supply 
74, 78
24 V~0 
Power supply 
1 ─ 8  AO1 ─ AO8 Analog outputs 1 ─ 8 
9 ─ 18
GND 
Ground. All grounds are connected 
internally to each other 
21, 22
N.C. 
Do not use! 
25, 26
 
Shield connection (functional earth), 
internally connected to the DIN rail 
 
NOTE: 
Shield connection to be used for shielded I/O 
cables only. It is not allowed to connect a 
L
ON
W
ORKS
 shield. 
 
Technical Data 
Output status LEDs behavior 
Table 29. Analog Output Module status LED behavior 
automatic mode 
brightness follows the 
commanded output signal 
override mode 
flashes