- 72 -
Wall Mounted Multi-Zone Split System Air Conditioner
Troubleshooting Guide
Error Code
■ Trouble Shooting
Error
Description
Cause of error
Check point & Normal condition
code
01
Indoor air sensor
02
Indoor inlet pipe sensor
06
Indoor outlet pipe sensor
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 10K
Ω / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5K
Ω/ at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5K
Ω/ at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Ω
10K
Ω
2.5Vdc
Check the resistance / voltage
V
❑ Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor
3. If the resistance of the sensor is 10K
Ω/5KΩ at 25°C(77°F), then sensor is normal
4. If the resistance of the sensor is 0 K
Ω or ∞, then sensor is abnormal. ➔ Change the sensor.
5. Plug the sensor onto the Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc / at 25°C(77°F), then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. 
➔ Repair or Change the PCB