Honeywell MS4103 사용자 설명서

다운로드
페이지 268
79
D2 and D3 Series
D2 series is an ultra-low leakage 
control damper which includes 
blade and jamb seals. The D3 
series is a general purpose damper 
intended for applications where low 
leakage performance is not 
necessary. 
SPECIFICATIONS
Size Range
1
Minimum Size
One Blade  ......................................... 6 in. wide by 6 in. high
Two Blade .......................................... 6 in. wide by 10 in. high
Maximum Size
Single Section  ................................... 48 in. wide by 72 in. high
Multiple Section ................................. unlimited
Temperature Rating ........................... 180 F (82 C) maximum
Standard Construction
2
Blade: ................................................ 16 gauge galvanized steel 3-V
Action:  ............................................... Parallel or Opposed
Frame
2
: .............................................. 16 gauge galvanized steel 
Hat-channel
Bearings
2
  .......................................... Synthetic (Acetal)
Linkage .............................................. Side linkage out of airstream 
(concealed in frame)
Axles .................................................. 1/2 in. square plated steel
Jamb Seals
3
 ...................................... Compression-type Stainless 
Steel
Blade Edge Seals
2
 ............................ Extruded Vinyl
1
Width and height dimensions furnished 1/4 in. undersized - standard
2
See table for customized options
3
D2 Dampers only
FLANGE OPTIONS
Honeywell International, Inc. certifies that the 
models D2, and D3 shown herein are licensed 
to bear the AMCA Seal. The ratings shown are 
based on tests and procedures performed in 
accordance with AMCA Publication 511 and 
comply with the requirements of the AMCA 
Certified Ratings Programs. The AMCA 
Certified Ratings Seal applies to air 
performance ratings only. March 2008.
Performance Data
D2, D3 Pressure and Velocity Limits.
DIMENSIONS DIAGRAM
LEAKAGE RATE
NOTE:
D2 and D3 will withstand higher pressures and velocities. Displayed 
ratings are conservative to prevent misapplication. Consult Honeywell 
if you have an application outside these limitations.
M18986
STANDARD
(NO FLANGE)
ACTUA
TOR SIDE FOR
INTERNAL
 MOUNTING
SINGLE
FLANGE
SINGLE
REVERSE
FLANGE
ACTUA
TOR SIDE FOR
INTERNAL
 MOUNTING
DOUBLE
FLANGE
Damper Size
in in.
Maximum 
System Pressure
Maximum 
System Velocity
12 x 12
5.0 in. wg
3000 fpm
24 x 24
5.0 in. wg
3000 fpm
36 x 36
4.0 in. wg
2500 fpm
48 x 48
2.5 in. wg
2000 fpm
H
W
M20587
1.0
.8
.6
.5
.4
.3
.2
6.0
5.0
4.0
3.0
2.0
1
M23317A
 2
3
5 6  8 10
20 30
50  
60
80 
100
AIR LEAKAGE (CFM/FT2)
ST
ATIC PRESSURE DIFFERENCE (IN. WG)
40
4
150
D3
D2
Rectangular Volume Control Dampers
D2 and D3 Series
S
ubmitt
al Sheet
S