Honeywell R0512 사용자 설명서

다운로드
페이지 86
ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
26 
 
 
Pull-Up Resistor Handling 
Table 10. Pull-up resistor handling 
 
device 
pull-up 
input 
circuit 
diagram 
(Fig. 14)
 
load-free voltage 
voltage  hardware 
de-
activated 
by @ (8) 
configured 
by DIP 
switch 
configured 
by plug-in 
activated 
for DI on AI 
with NTC 
or low-
impedance 
input 
for voltage 
input or 
high-
impedance 
input 
XF830A 
10 V 
optional 
switch-off 
YES 
NO 
NO 
YES 
case 1 
8.89 V 
0 V 
XFU830A 
XF821A 
XFL821A 
YES 
XF521, 
XF521A 
fixed 
NO 
NO 
case 2 
8.89 V 
XF526 
XFL521, 
XFL521A/B 
optional 
switch-off 
YES
(3
 
YES 
config.
(6
 
case 1 
0 V 
Smart I/O 
XFC 
5 V 
YES
(4
 
YES
(7
 
case 3 
5 V 
XL20 
10 V 
fixed 
NO 
NO 
YES 
case 2 
8.89 V 
8.89 V 
XL50 
optional 
switch-off 
YES
(2
 
YES
(5
 
case 1 
0 V 
XL100, 
XL100A 
fixed 
NO 
YES 
case 2 
8.89 V 
XL100B 
optional 
switch-off 
YES 
configurable 
case 1 
0 V 
XL100C 
YES
(1
 
NO 
YES
(5
 
(1
 controller firmware 
≥ 2.03; 
(2
 controller firmware 
≥ 2.02; 
(3
 controller firmware 
≥ 2.03 (local/shared mode), CARE ≥ 5.00.01 (open mode); 
(4
 CARE 
≥ 5.00.01; 
(5
 controller firmware < 2.04; 
(6
 controller firmware < 2.04 (local/shared mode), CARE 
≥ 5.01.xx (open mode); 
(7
 
CARE ≥ 5.01.xx; 
(8
 Assigning "@" as first digit of input characteristic name (e.g.: "@0-10V") in the CARE text editor disables the pull-up resistor. 
When using the XF821A/XFL821A for current inputs, be sure to assign "@" as the first digit of the input characteristic name. 
 
A
D
18.2 k
(pull-up)
Ω
100 k
Ω
100 k
Ω
5 V
A
D
24.9 k
(pull-up)
Ω
150 k
Ω
49.9 k
Ω
10 V
A
D
24.9 k
(pull-up)
Ω
150 k
Ω
49.9 k
Ω
10 V
Case 1
Case 2
Case 3
 
 
Fig. 14. Input circuit diagram 
 
 
Last Change 
In the attribute "Last Change", the last change of state of a digital input/output is 
stored with the time and date.