Honeywell R0512 사용자 설명서

다운로드
페이지 86
ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
32 
 
•  As soon as an alarm occurs (e.g. through exceeding a limit value), the attribute 
"Point in Alarm" is set to "Yes". The attribute is immediately set back to "No" 
when the limit value returns to normal. 
 
 
 
Pulse Duration 
The attribute "Pulse Duration" is used for the pulsed subtypes of the digital output 
(i.e. "Pulse 1") and flexible datapoints of the type "Pulse 2". It defines the duration 
between coming and going edge of a pulsed signal. The values for this attribute can 
vary from 1 to 255 seconds; the resolution is 1 second. The default value is 1 
second. 
 
NOTE: 
After a power failure or disconnection of the controller, the “Pulse 1” and 
“Pulse 2” outputs will resume their last output pulse behavior before the 
outage. 
 
 
Safety Position (XFx822x, XFx824x, and XFx830x modules) 
The analog output modules XF822x/XFL822x/XFLR822x, the relay output modules 
XFL824x/XFL824x/XFLR824x and the mixed I/O modules XF830x/XFU830x support 
the “Safety Position” attribute, which can be set in the CARE datapoint editor. 
The modules will put the outputs into the safety position as soon as communication 
with the Excel 800 CPU is lost. 
The XF822x/XF824x modules detect this lost communication once no more polls 
are received from the Excel 800 CPU for more than one second. 
The XFL822x/XFL824x and XF830x/XFU830x modules detect this lost 
communication once no more polls are received from the Excel 800 CPU within the 
heartbeat time of the module. 
 
XF822x/XFL822x –”The following attribute options are provided: 
 
•  “0%”  equals 0 Vdc or 2 Vdc (0…11 Vdc or 2…11 Vdc characteristic) 
•  “50%”  equals 5 Vdc or 6 Vdc (0…11 Vdc or 2…11 Vdc characteristic) 
•  “100%” equals 10 Vdc 
•  “Remain in last position” (this is the default setting). 
 
XF824x/XFL824x and XF830x/XFU830x –”The following attribute options are 
provided: 
 
•  “Off (logical)” 
•  “On (logical)” 
•  “Remain in last position” (this is the default setting). 
 
NOTE: 
When the XFL822x/XFLR822x and XFL824x/XFLR824x modules are 
used with non-Excel 800 controllers, the Safety Position can only be set 
in the L
ON
W
ORKS
 NV settings in CARE, and not in the CARE datapoint 
editor. 
 
 
Scaling Factor 
Input pulses from utility meters (gas, water, heat, etc.) can be connected to the 
totalizer inputs using the attribute "Scaling Factor". The pulses supplied by the 
meters are multiplied by the scaling factor and are then ready to be read as pure 
consumption values. The "Scaling Factor" thus always indicates the value of each 
pulse received. The adjustable range is 0.0 through 100,000,000.0, 
The number of decimal places depends on the selected engineering unit. 
 
 
 
Example: 
A heat meter supplies 10 pulses per kWh "consumed". Accordingly, the scaling 
factor (= value of a pulse) is 0.1 kWh/pulse.