Honeywell R0512 사용자 설명서

다운로드
페이지 86
COMMUNICATION 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
56 
 
synchronization process. Any new device added to the system bus will adopt the 
bus system time. 
 
NOTE:
 
If you enter the time on the local MMI of an older device (prior to 
V2.0.xx), synchronization will not be carried out. Even the locally entered 
time might be overwritten by a synchronization coming from a newer 
device (V2.0.xx or higher). 
 
 
Point Refreshing 
Excel controllers provides a refresh mechanism (that is adapted to the Token 
timing) for sending the values of the attributes "Value", "Manual Value", "Operating 
Mode", and "Alarm Status" to either an MMI interface or to a front-end. (A maximum 
of two point refresh messages can be sent while the controller is holding the 
Token.) 
 
 
PC Communication 
An Excel 50/100/500/600/800 system can also accommodate a PC connected to 
the C-bus. Multi-master communication is still supported and token passing 
continues between the individual bus devices. The C-bus treats controllers as being 
equal in rank to a PC. 
 
 
Excel IRC 
Excel controllers support communication with the Excel IRC control system. This 
system monitors and controls individual rooms within a building. The Excel IRC 
system communicates on the C-bus via its Multicontroller (MC). The Application 
control functions for Excel IRC, called ACFs, are all processed by the MC. 
See EXCEL 5000 IRC Integration System Overview and Application Guide,  
EN3R-1182GE51, for additional information. 
 
 
Remote Communication 
Excel 50/100/500/600/800 controllers are all able to communicate to remote 
building supervisors via an analog or ISDN modem connected to them. This allows 
two-way communication between the building supervisors and the controllers. The 
Excel 100/500 controllers can store the numbers and passwords for up to three 
supervisors and can call them in response to critical alarms or other programmed 
triggers, or the supervisor can call at any time for status, trend, or alarm 
information. 
 
 Disable dial-out (V2.04.xx or higher) 
Automatic upload of the remote trend buffer can be disabled by a remote front-end 
(XBS 1.6.0 or higher). In this case, remote trend values are stored in the buffer, with 
newest values overwriting oldest when the buffer is full, but the controller does not 
dial out to send remote trend buffer level alarms or to flush the buffer. The controller 
will still dial out for critical and uncritical alarms. 
Excel 100 and 600 controllers and Excel 500 controllers with V1.5.xx firmware or 
earlier can, when operating as stand-alone controllers, make use of the XDM506 
modem submodule mounted on the CPU board. The XDM506 can perform all of the 
functions of the XM100A in providing remote communication capability with up to 
three building supervisors. 
 
 
Direct modem connection 
 
(Excel 50/500, 
  
V2.01.xx or higher and 
 
Excel 800, V3.00.xx or higher) 
Excel 50/500 controllers with firmware version V2.01.xx or higher, Excel 100C 
controllers, as well as Excel 800 controllers with firmware version V3.00.xx or higher 
have the advantage of allowing direct connection of a modem or ISDN terminal