Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–40
Overload Advance Notice Signal
When the output current exceeds a preset 
value, the [OL] terminal signal turns ON. 
The parameter C041 sets the overload 
threshold. The overload detection circuit 
operates during powered motor opera-
tion and during regenerative braking. The 
output circuits use open-collector 
transistors, and are active low.
[OL] 
Signal
1
0
ON
t
ON
Current
threshold
regeneration
power running
threshold
C041
C041
Option 
Code
Terminal 
Symbol
Function Name
Output 
State
Description
03
OL
Overload Advance 
Notice Signal
ON
when output current is more than the set thresh-
old for the overload signal
OFF
when output current is less than the set threshold 
for the overload signal
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
C041
Notes:
The default value is 100%. To change the level 
from the default, set C041 (overload level).
The accuracy of this function is the same as the 
function of the output current monitor on the [FM] 
terminal (see 
The example circuit for terminal [12] drives a relay 
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from 
damaging the inverter’s output transistor.
RY
+
Example (requires output configuration—
see page 
Inverter output 
terminal circuit
OL
Example for terminals [AL0], [AL1], [AL2] 
(requires output configuration—
see pages 
 and 
AL0
AL2
AL1
Inverter logic 
circuit board
See I/O specs 
on page 
OL
Load
Power
supply
12 11
CM2