Instructions for the installer 
 
8
 
3.2  Gas connection 
 
 
This appliance is suitable for installation with Natural Gas or ULPG (propane). 
Refer to page 13 for the relevant burner pressure and appropriate injector sizes. 
When the appliance is to be connected to Natural Gas then the pressure 
regulator supplied must be fitted to the gas inlet. A test point (for checking the gas 
pressure) is supplied either with the regulator or as a separate fitting in the case 
of LPG (propane) appliances. 
Connection of the appliance to the gas supply must be in accordance with the 
requirements of AS5601. A ½” BSP connector at the inlet is recommended and 
the gas supply line to the appliance must be of adequate length to allow sufficient 
withdrawal of appliance for service or disconnection and be: 
1.
  annealed copper pipe or; 
2.
  Flexible hose according to AS/NZ1869 & be at least Class “B”, 10 mm 
diameter, max length 100 mm. 
 
The cooker must be installed with provision to allow the gas to be turned off and 
disconnected for servicing and removal of the appliance as required from the gas 
supply. 
Before the cooker is operated make certain all relevant parts are placed in the 
correct position. 
When the installation is completed the installation connections of cooker will 
require to be leak tested, the burner operating pressure and flame checked and 
adjusted. 
Warranty service calls do not cover these adjustments! 
To check the operating pressure of the appliance it is recommended at least 2 
large size burners are used. Ensure appliance is secured to wall when installation 
is completed. 
N.G. The regulator supplied must be fitted to the ½ BSP thread at the rear of the 
appliance. An approved manual shut-off valve must be installed. The N.G. 
regulator must be checked and adjusted to 1.0kPa after installation. 
 
U.L.P.G. Can be connected to the inlet fitting directly. The pressure must be 
checked to ensure it is operating at 2.75kPa. A separate test point fitting must 
be installed between the piping & the appliance for the pressure to be checked 
to ensure it is operating at 2.75kPa.