OPERATION
FREEZER CABINETS
The  electronic  temperature  control  constantly  monitors  box 
temperature as well as evaporator coil temperature to maintain 
consistent product temperatures.
At  initial  start-up  or  anytime  power  is  disconnected,  then 
reconnected to the unit, the control will delay all operations for 
a short time (up to 10 minutes.)  While in this delay period, the 
control initializes the control parameters and confirms that the 
temperature sensors and circuits are operational.
REGARDING  FREEZERS:    After  initializing,  the 
control will immediately enter a DEFROST mode.  
The compressor and condenser fan as well as the 
evaporator  fan  will  remain  off  until  initialization 
defrost is complete.  This initial defrost cycle may 
take up to 15 minutes to complete, at which time 
the freezing cycle will begin.
The control is located in the rear of the cabinet (See Figure 6.). 
Freezers  are  factory  set  at  mid-range  to  maintain  about  -3ºF  
(-19ºC)  box  temperature.  To  adjust  for  colder  temperatures, 
turn the knob clockwise.  For warmer temperatures, turn the 
knob counter-clockwise.  Turn the knob fully counter-clockwise 
to turn the refrigeration system off.  Never turn the knob more 
than 1 dial number and always allow 8 hours for temperature 
stabilization before making any additional adjustments.
Freezer cabinets with two evaporators have counter-rotating fans 
to ensure even airflow throughout the cabinet. The left evaporator 
has a CCW motor and a clear fan blade and the right evaporator 
has a CW motor and a black fan blade.
The evaporator fan(s) and condenser fan will cycle off and on 
with the compressor to conserve energy.
Freezer:
Whenever the freezer is plugged in, and the control has completed 
initializing including the initial defrost cycle.  The temperature 
control  will  cycle  the  compressor  and  condenser  fan  motor 
and evaporator fan motor to maintain box temperature at the 
control setting.
Freezer Automatic Defrost
The control also monitors compressor total running time and 
will enter a defrost cycle after total compressor running time is 
greater than 4-hours since the last defrost cycle OR if evaporator 
coil temperature drops below -34ºF (-37ºC) (indicating excessive 
frost on the coil.)
When the control enters the defrost mode, it switches off the 
evaporator fan motor, compressor and condenser fan motor, and 
switches on the defrost heater to warm the evaporator coil. Thereby 
melting all frost accumulated during the previous refrigeration 
cycle.  The control will continue the defrost cycle for a MINIMUM  
of 8 minutes and a MAXIMUM of 30 minutes depending on the 
amount of frost accumulated on the evaporator coil.
After the defrost cycle is complete, the control returns to a normal 
refrigeration cycle, however the evaporator fan motor will not 
switch on for 2 minutes AFTER the compressor and condenser 
fan motor have begun operating. 
Freezer Manual Defrost
If a manual defrost is desired, simply unplug the unit for several 
seconds, then plug unit back in.  This will cause the control to 
re-initialize and then enter a defrost cycle.