sensor temperature defrost termination temperature
or defrost duration (F1) ends, the heater and defrost
will stop after the draining time (F6). The cold‐room
temperature (set temperature + hysteresis), the
compressor will starts and go back to refrigeration
status.
When the defrost interval time (f2) is set”00”, the
function of the automatics defrost will be cancelled.
Temperature displayed when defrost: If F4 is set “01”, it
displays the temperature when the defrost starts. After
defrost, It will continue to display this temp for 20 min
and the defrost LED will begin flashing. It will then come
back to normal temperature.
• Controlling the evaporator fan after defrost:
or defrost duration (F1) ends, the heater and defrost
will stop after the draining time (F6). The cold‐room
temperature (set temperature + hysteresis), the
compressor will starts and go back to refrigeration
status.
When the defrost interval time (f2) is set”00”, the
function of the automatics defrost will be cancelled.
Temperature displayed when defrost: If F4 is set “01”, it
displays the temperature when the defrost starts. After
defrost, It will continue to display this temp for 20 min
and the defrost LED will begin flashing. It will then come
back to normal temperature.
• Controlling the evaporator fan after defrost:
Controlling by time: When F7 is set “00” after
defrost, the compressor works for F8 and then the
fan restarts. After defrost and the first working
mode, the fan will follow the mode of F5.
Controlling by temperature: When F7 is set “01”
after defrost, when the evaporator temperature
reaches F9, the fan restarts. After defrost and the
first working mode, the fan will follow the mode of
F5.
defrost, the compressor works for F8 and then the
fan restarts. After defrost and the first working
mode, the fan will follow the mode of F5.
Controlling by temperature: When F7 is set “01”
after defrost, when the evaporator temperature
reaches F9, the fan restarts. After defrost and the
first working mode, the fan will follow the mode of
F5.
• Sensor failure work mode: If the cold‐room sensor is
short circuited or overheated, “HH” will be
displayed. If the cold‐room sensor is in an open
circuit or the temperature is too low then “LL” is
displayed. At that time the compressor will
automatically go to a cycle of 45 min on and 15 min
off. When the evaporator sensor fails or surpasses
the displayed range, the defrost termination will be
just controlled by the defrost duration.
displayed. If the cold‐room sensor is in an open
circuit or the temperature is too low then “LL” is
displayed. At that time the compressor will
automatically go to a cycle of 45 min on and 15 min
off. When the evaporator sensor fails or surpasses
the displayed range, the defrost termination will be
just controlled by the defrost duration.