Carrier 30XW325-400 사용자 설명서

다운로드
페이지 32
15
Carrier’s packaged selection program provides quick,
easy selection of Carrier’s water-cooled chillers. The pro-
gram considers specific temperature, fluid and flow
requirements among other factors such as fouling and alti-
tude corrections.
Before selecting a chiller, consider the following points:
Leaving water (fluid) temperature (LWT)
• The LWT must be at least 40 F (4.4 C) or greater.
• If the LWT requirement is greater than 60 F (15.5 C), a
mixing loop is required.
Entering water (fluid) temperature (EWT)
• If the EWT requirement is greater than 70 F (21.1 C), a
mixing loop is required. The EWT should not exceed
70 F (21.1 C) for extended operation. Pulldown can be
accomplished from 95 F (35 C).
Evaporator flow rate or evaporator delta-T:
• The evaporator delta-T (EWT – LWT) must fall between
5 and 20° F (2.8 and 11.1° C) while still meeting the
maximum entering requirements.
• For larger or smaller delta-T applications, a mixing loop
is required.
 If the evaporator flow is variable, the rate of
change of flow should not exceed 10% per minute.
The loop volume in circulation must equal or exceed
3 gallons per nominal ton (3.2 L per kW) of cooling for
temperature stability and accuracy in normal air condi-
tioning applications. In process cooling applications,
there should be 6 to 10 gallons per ton (6.5 to 10.8 L
per kW). To achieve this loop volume, it is often neces-
sary to install a tank in the loop. The tank should be baf-
fled to ensure there is no stratification, and that water
(or brine) entering the tank is adequately mixed with liq-
uid in the tank. See Water Loop Volume in the Applica-
tion Data section.
Evaporator pressure drop:
• A high evaporator pressure drop can be expected when
the evaporator delta-T is low. A mixing loop can help to
alleviate this situation.
• The three-pass evaporator option is recommended to
increase performance when the evaporator delta T is
high. This is particularly helpful with brine applications.
Condenser pressure drop:
• A high condenser pressure drop can be expected when
the condenser delta-T is low. A one-pass condenser can
help lower pressure drop.
Series chillers:
• One-pass heat exchangers can help lower pressure
drop when heat exchangers are placed in series.
Water quality, fouling factor:
• Poor water quality can increase the required evaporator
fouling factor.
• Higher than standard fouling factors lead to lower
capacity and higher input kW from a given chiller size
compared to running the same application with better
water quality (and lower fouling factors).
Temperature reset:
• Return water (standard)
• Outside air temperature (standard)
• Space temperature (accessory sensor required)
• 4 to 20 mA (requires an energy management module)
Demand limit:
• 2-step (requires an energy management module)
• 4 to 20 mA (requires an energy management module)
• CCN Loadshed
Performance data
EVAPORATOR AND CONDENSER FLOW RATES
*Maximum condenser fluid temperature shown for standard condensing
option. Heat machine option may have leaving fluid temperatures up to
140 F (60 C).
30XW UNIT
EVAPORATOR
CONDENSER
NOMINAL
Leaving Fluid/Entering Fluid
Minimum Entering 
Fluid
Maximum Leaving 
Fluid
Evaporator
Condenser
Minimum
Maximum
40 F (4.4 C)/
45 F (7.2 C)
60 F (15.6 C)/
70 F (21.1 C)
65 F (18.3 C)
118 F (47.8 C)*
Minimum
Flow Rate
Maximum
Flow Rate
Minimum
Flow Rate
Maximum
Flow Rate
Nominal
Flow Rate
Nominal
Flow Rate
GPM
L/s
GPM
L/s
GPM
L/s
GPM
L/s
GPM
L/s
GPM
L/s
325
Two pass
411
25.9
1481
93.4
494
31.1
1974
124.5
790
49.8
987
62.3
One pass
790
49.8
3126
197.2
987
62.3
3290
207.6
790
49.8
987
62.3
Three pass
247
15.6
987
62.3
790
49.8
350
Two pass
433
27.3
1557
98.2
519
32.7
2076
131.0
830
52.4
1038
65.5
One pass
830
52.4
3287
207.4
1038
65.5
3460
218.3
830
52.4
1038
65.5
Three pass
260
16.4
1038
65.5
830
52.4
400
Two pass
486
30.7
1751
110.4
584
36.8
2334
147.3
934
58.9
1167
73.6
One pass
934
58.9
3696
233.1
1167
73.6
3890
245.4
934
58.9
1167
73.6
Three pass
292
18.4
1167
73.6
934
58.9
Selection procedure