Top Mount Packaged Refrigeration System | Outdoor
Refrigeration/Defrost Sequence of Operation
The sequence of operation varies depending on the model that has been installed. The three basic models are Low Temperature, Medium 
Temperature, and High Temperature models. The particular model can be determined by the seventh digit of the model number. See Tables  
1-3 for details and settings.
Control of the refrigeration and defrost system is provided by the Carel controller along with a space (box) temperature sensor and a coil 
(defrost) temperature sensor. The controller will control on and off switching for the compressor, condenser fan motor(s) (cycles with the 
compressor), evaporator fan motor(s) and electric defrost heaters for electric defrost.
The Carel controller is pre-programmed for all three applications. This is done with the use of the parameter list. The parameter list can be 
changed by entering the Carel Controller and changing the “EZY” setting. See page 15.
Status
Compressor
Condenser
Fans
Evaporator
Fans
Defrost
Heaters
Notes
Off
Display alternates “OFF”  and Room 
Temperature
Off
Off
Off
Off
If unit shows “OFF”, depress 
the “^” button and hold for 
three seconds.
On
Automatic Defrost on start up
Off
Off
Off
On
If coil temperature is below 
65° F.  If it is above, defrost is 
not initiated.  Drip Time and 
Freeze Time are ignored.
On
Defrost Sensor reaches 65° F and 
defrost is terminated
Off
Off
Off
Off
On
Cooling cycle initiated - Drip Time 
Off
Off
Off
Off
System Timer Begins/ 2 min 
drip time
On
Drip Time of 2 minutes ends - coil 
freeze begins
On
On
Off
Off
Compressor 
starts 
and 
evaporator  fans  delay  for  2 
minutes  to freeze the coil.
On
Evaporator fans start after 2 min 
delay
On
On
On
Off
On
Box Temperature (-10.1° F) is 
satisfied
Off
Off
On
Off
On
Box Temperature rises to -8.0° F
On
On
On
Off
2° F Differential,  Minimum 
Compressor Off time is 4 
minutes
On
Defrost Initiated (Manually or 6 
hour counter)
Off
Off
Off
On
Electric Defrost
On
Cooling cycle initiated - Drip Time
Off
Off
Off
Off
System Timer Begins/ 2 min 
drip time
On
Drip Time of 2 minutes ends - coil 
freeze begins
On
On
Off
Off
Compressor starts and 
evaporator fans delay for 2 
minutes  to freeze the coil.
On
Evaporator fans start after 2 min 
delay
On
On
On
Off
TABLE 5
Model PTT | Low Temperature Models | EZY SETTING =1
SET POINT IS -10° F
These models are intended for freezer applications and require electric defrost.
3.
C
on
tr
ollers