This section provides a brief description of the key controls 
and accessories found in this boiler.
See  Figure 26, Page 41  for detailed sequence of operation. 
See the Repair Parts Manual for locations of all control 
components and accessories described.
Integrated Boiler Control (IBC)
Integrated Boiler Control (IBC) is a microprocessor based 
controller for high effi ciency gas boiler that monitors 
all safety controls and which controls operation of the 
combustion air blower, circulator pump, burner, and 
a combination direct spark igniter/fl ame sensor. This 
controller is not intended for use with a vent damper. 
Controller is mounted on control panel inside of boiler and 
contains a three character user interface display.
High Limit Control
High Limit Control determines maximum boiler water 
temperature and also provides means for protecting boiler 
and heating system from unsafe operating conditions which 
could damage boiler. 
Limit control sensor is mounted in ¾” NPT control well on 
top of the front boiler section at hot water outlet. 
Limit control is incorporated in IBC and is fi eld adjustable 
between 80°F and 190°F. 
Field setpoint adjustment for each installation depends on 
heating system requirements. 
Limit Control automatically resets when boiler water 
temperature decreases (10-30°F adjustable differential). 
Differential can be adjusted to provide fl exibility for boiler 
operation. Larger the differential, longer run cycle of boiler.
Thermal Purge Operation
1. 
Thermal purge feature complies with 2012 DOE 
and NRCan requirements that boiler control must 
incorporate automatic means to adjust water 
temperature.
2. 
Intent of thermal purge is to insure usable residual 
heat in the boiler is circulated until it is suffi ciently 
depleted from the system before the burner is allowed 
to fi re.  To that end, on call for heat, burner is held 
off while circulator runs until boiler temperature drops 
to thermal purge temperature limit or time delay is 
exceeded. Both of these parameters are adjustable.
3. 
When boiler temperature falls below thermal purge 
temperature limit or time delay expires, burner is 
allowed to fi re.
In addition to thermal purge temperature and thermal 
purge time delay parameters, two other conditions release 
integrated boiler controller from thermal purge and allow 
burner to run in order to maintain comfort in the space.
• Boiler temperature has dropped 10°F from boiler water 
temperature measured at beginning of the call for heat.
• Boiler temperature is cooling at a rate greater than 
5°F/minute while circulator is running.
4. 
For Installations using Indirect Hot Water Heater
Depending on the specifi c installation, thermal purge 
delay might or might not affect end user’s expectation for 
domestic hot water delivery. In event the customer has a 
concern that it takes too long for hot water, the situation 
may be resolved in three ways.
A.  Add a Domestic Hot Water Module, ECR part 
Number 240009562 (Honeywell part number 
W8375s1008). This control senses when hot water 
is being drawn, and instructs the integrated boiler 
control to bypass the thermal purge operation until 
domestic how water draw ends. Thermal purge will 
then be re-enabled.
DHW module incorporates a temperature sensor 
installed at the indirect water heater’s hot water 
supply fi tting ( Note - this sensor is in addition to, 
not in place of, the limit control on the hot water 
tank.) The Module is connected to the Enviracom 
terminals in the Integrated Boiler Control.
B.  Thermal purge parameters may be adjusted (higher 
thermal purge temperature limit and/or shorter 
thermal purge time delay) to bring the burner on 
sooner.
C.  Thermal purge function can be disabled.
Gas Control Valve
Electrically controlled Combination Gas Control Valve is 
designed to meet requirements for use with direct ignition 
systems found in this boiler. Valve is piped to gas/air mixer.
Direct Spark Igniter
Direct spark igniter utilizes a spark gap to initiate gas 
combustion in the burner. Igniter is mounted next to burner 
through gas/air mixer. The igniter also serves as means for 
proving main burner fl ame by fl ame rectifi cation. In the 
event of a lack of fl ame signal on three (3) consecutive tri-
als for ignition, IBC will lockout and display Error Code 62. 
Draft Inducer Temperature Safety Switch
Draft Inducer Temperature Safety Switch is a disc 
thermostat (180 °F setpoint) located on induced draft fan 
outlet port. Switch protects inducer and vent pipe from 
potential high temperature condition for discharging fl ue 
gases. Condition would typically be result of higher high 
limit control setting or over fi ring. Temperature safety 
switch automatically resets when the vent temperature 
decreases. (15 °F switch differential).
CONTROLS AND ACCESSORIES