• Following steps and diagram indicate locations of 
connection points required to check differential air 
pressure.
• Differential air pressure switch is safety device which 
prevents boiler from fi ring if there is air intake, boiler 
heat exchanger or vent blockage.
• Turn off service switch, or lower thermostat setting.
• Remove vinyl caps from Tee and 4-way connector.
• Install testing lines as shown to inclined manometer or 
differential pressure gauge with ability to read 0.01” to 
3.0” w.c.
• Turn on service switch and set thermostat to call for 
heat.
BOILER 
STATUS
DIFFERENTIAL 
PRESSURE (W.C.)
PRESSURE 
SWITCH 
CONNECTS
Not Running
0”
Normally Open
Setpoint
1.00” for Model-100
1.60” for Model-75
2.10” for Model-50
Running 
Without 
Blockage
Greater Than         
Setpoints
Closed
Running 
With 
Blockage
Less Than or Equal to 
Setpoints
Open
If manometer readings do not correspond to chart above, 
check for possible causes:
• - Blockage or moisture in suction lines
• - Blockage in air intake or vent pipes
• - Undersized air intake or vent pipes
• - Loose blower wheel or motor shaft
• - Incorrect pressure switch or pressure switch setpoint
When pressure reading is proper and the pressure switch is 
operating properly, remove testing lines and reinstall vinyl 
caps to Tee and 4-way connector.
 DIFFERENTIAL AIR PRESSURE SWITCH CHECK