Lochinvar 162 1 전단

다운로드
페이지 2
Copper-Fin
®
 Boiler Dimensions & Specifications
CBN-07  
(Replaced  CBN-06  3/10)
FG-10M-5/11-Printed in U.S.A.
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
Standard Features
• 
81% Thermal Efficiency
• 
Electronic Temperature Control
• 
Fan Assisted Combustion
• 
Sealed Combustion Chamber
• 
Stainless Steel Burners
• 
Low NOx Operation Exceeds the most
Stringent Air Quality Requirements
• 
ASME Copper Finned Tube
Heat Exchanger
• 
160 psi Working Pressure
• 
Gasketless Heat Exchanger Design
• 
Pump Relay w/ Delay
• 
Down Stream Test Valve
• 
Referenced Gas Valves
• 
Loch-Heat Ceramic Tile 
Combustion Chamber
• 
Hot Surface Ignition
• 
Adjustable High Limit w/ Manual Reset
• 
ASME Pressure Relief Valve
• 
Temperature & Pressure Gauge
• 
Flow Switch
• 
24 Volt Control System
• 
BMS Terminal Strip
• 
Combustion Air Filter
• 
Freeze Protection
• 
10 Year Limited Warranty on Heat 
Exchanger (See warranty for details)
Optional Equipment
• 
Alarm Bell
• 
Contacts on any Failure
• 
Contacts for Air Louvers
• 
Cupro-Nickel Heat Exchanger
• 
High & Low Gas Pressure Switch 
   w/ Manual Reset
• 
Outdoor Reset Control
• 
Manual Reset Low Water Cut-Off
  w/  test
• 
Stack Frame
 MP
2
 Sequencer
Available Firing Systems
M9 
Hot Surface Ignition with 
     
Electronic Supervision (Standard)
M13 GE 
GAP/FM/CSD1
M7 California 
Code
Venting
• 
Outdoor Vent Cap
Registered under U.S. Patent # 5,989,020
For Ease In Ordering
By Model Number
C B   N   0 4 9 7   M 9
MODEL
Btu/hr
 INPUT
This boiler is a 495,000 Btu/hr,
natural gas Copper-Fin. 
It has M9 firing controls
NAT. GAS
FIRING
CONTROLS
Copper-Fin Heating Boiler 
 
 
 
Dimensions & Spec i fi ca tions
 Input 
 
 
Heating 
Net
  Model  Max  Thermal Capacity I=B=R 
 
 
 
 
 
 
 
  Gas  Vent  Shipping
 Number  MBH Efficiency  MBH 
MBH 
G    Conn.  Size  Weight
CBN0497 
495 
81% 
401 
349 
31-1/2”  45-1/4”  22-1/4”  12-1/2”    9-1/2” 
22-3/4”  29-1/2”  1-1/4” 
6” 
440
CBN0647 
645 
81% 
522 
454 
31-1/2”  56-3/4”  22-1/4”  12-1/2”    9-1/2” 
28-1/2”  29-1/2”  1-1/4” 
8” 
510
CBN0747 
745 
81% 
603 
524 
31-1/2”  64” 
22-1/4”  12-1/2”    9-1/2” 
32” 
29-1/2”  1-1/4” 
8” 
550
CBN0987 
985 
81% 
798 
694 
36” 
48-1/4”  33-1/2”  15-3/4”    8-1/2” 
  8-1/2”  33-3/4”  2” 
10” 
845
CBN1257 
1255 
81% 
1,017 
884 
36” 
58-1/2”  33-1/2”  15-3/4”    9-1/2” 
10-1/2”  33-3/4”  2” 
12” 
905
CBN1437  1435  81% 
1,162  1,010  36”  68-3/4” 33-1/2”  15-3/4” 10-1/2”  10-1/2” 33-3/4” 2” 
12”  1050
CBN1797 1795  81%  1,454  1,264 36”  82-1/4” 
33-1/2” 15-3/4” 
11”  11”  33-3/4” 
2”  14”  1193
CBN2067 2065  81%  1,673  1,455 36”  92-1/2” 
33-1/2” 15-3/4” 
11”  11”  33-3/4” 
2”  14”  1350
Notes:  Change ‘N’ to ‘L’ for LP gas models.    
 
Water connections for models CB 0497-747 are 2” NPT on 6-1/2” centers. 
 
No deration on LP models. 
 
 
 
Water connections for models CB 0987-2067 are 2-1/2” NPT on 11-1/4” centers.
Performance data based on manufacturer test results.