Belkin belkin bulldog plus- shutdown management software for windows 사용자 설명서
SNMP Trap Number:
Variable Trap
No.
Description
dupsCommunicationLost
1
SEVER: Communication with the UPS failed
dupsCommunicationEstablished 2
INFORMATION:
Communication with the UPS reestablished
dupsPowerFail
3
WARNING: Power failed! The UPS is operating on battery power
dupsPowerRestored
4
INFORMATION: Power restored! The utility power restored
dupsLowBattery
5
SEVER: The UPS batteries are low and will soon be exhausted
dupsReturnFromLowBattery
6
INFORMATION: The UPS has returned from a low battery condition
dupsLoadWarning
7
INFORMATION: Loading percent of the UPS over the Load Warning
value
dupsNoLongerLoadWarning 8
INFORMATION:
Returned from Load Warning condition
dupsLoadSeverity
9
Warning: Loading percent of the UPS over the Load Severity value
dupsNoLongerLoadSeverity
10
INFORMATION: Returned from Load Severity condition
dupsLoadOnBypass
11
WARNING: The UPS loads on bypass
dupsNoLongerLoadOnBypass 12
INFORMATION: The UPS is not on bypass mod
dupsUPSFault
13
SEVER: A general fault caused in the UPS
dupsBatteryGroundFault
14
SEVER: The UPS battery ground fault
dupsNoLongerBatteryFault 15
INFORMATION:
The
UPS recovered from battery ground fault
dupsTestInProgress 16
INFORMATION: The UPS test in progress
dupsBatteryTestFail
17
SEVER: The UPS test in progress
dupsFuseFailure
18
SEVER: The UPS fuse failed
dupsFuseRecovered 19
INFORMATION: The UPS fuse recovered
dupsOutputOverload
20
SEVER: The UPS overload
dupsNoLongerOverload 21
INFORMATION:
Recovered from UPS overload
dupsOutputOverCurrent
22
SEVER: The UPS output is over current
dupsNoLongerOutputOverCurrent 23
INFORMATION: Recovered from UPS over current
dupsInverterAbnormal
24
SEVER: The UPS inverter is operating abnormally
dupsInverterRecovered 25
SEVER:
Recovered from UPS inverter abnormal state
dupsRectifierAbnormal
26
SEVER: The UPS rectifier is operating abnormally
dupsRectifierRecovered
27
INFORMATION: The UPS recovered from abnormal state
dupsReserveAbnormal
28
SEVER: The UPS rectifier is operating abnormally
dupsReserveRecovered 29
INFORMATION:
The
UPS rectifier is now operating normally
dupsLoadOnReserve 30
INFORMATION: The UPS load on reserve
dupsNoLongerLoadOnReserve 31
INFORMATION: The UPS no longer load on reserve
dupsEnvOverTemperature
32
WARNING: The environment is over normal temperature
DupsNoLongerEnvOverTemperatu
re
33
INFORMATION: The environment recovered from abnormal
temperatures
Belkin Components
33