DR4300 Circular Chart Recorder 
152 
DR4300 Circular Chart Recorder Product Manual 
12/03 
Step Description 
Press 
Action/Result 
Calibrate 0 % 
FUNC
 
 
You will see: 
APLY
Upper Display
 
INZERO
Lower Display
   
•  Adjust your calibration device to an output signal equal 
to the 0 % range value for your particular input type. See 
Table 5-1 for Voltage or Resistance equivalents. 
•  Wait 60 seconds, then go to the next step. 
Calibrate 100 % 
FUNC
 
You will see: 
  APLY
Upper Display
 
INSPAN
Lower Display
   
Adjust your calibration device to an output signal equal to 
the 100 % range value for your particular input type (see 
Table 5-1 for voltage or resistance equivalents). Wait 60 
seconds, then go to next step. 
Exit the Calibration Mode 
FUNC
 
The recorder stores the calibration constants.  
The value of input set up group parameter “LD CAL” is set 
to “FLD” (field). 
The recorder begins to use the new field calibration values 
for this channel. 
Repeat this procedure for the other pen, if required.