Product Characteristics 
 
4.7 SCALANCE X005 Technical Specifications 
 
Note 
The number of connected SCALANCE X Industrial Ethernet switches influences the frame 
propagation time. 
When a frame passes through SCALANCE X005, it is delayed by the store and forward 
function of the switch: 
- With a 64 byte frame length by approx. 10 µs (at 100 Mbps) 
- With a 1500 byte frame length by approx. 130 µs (at 100 Mbps) 
This means that the more SCALANCE X005 devices are passed through, the higher the 
frame propagation time will be. 
 
 