Product Characteristics 
 
4.2 SCALANCE X208 
4.2.5 
SCALANCE X208 Power Supply and Signaling Contact 
Power Supply 
The power supply is connected using a 4-pin plug-in terminal block. The power supply can 
be connected redundantly. Both inputs are isolated. There is no distribution of load. When a 
redundant power supply is used, the power supply unit with the higher output voltage 
supplies the SCALANCE X208 alone. The power supply is connected over a high resistance 
with the enclosure to allow an ungrounded set up.  
 
 
Figure 4-5 
SCALANCE X208 Power Supply 
 
 
 
Warning 
The SCALANCE X208 is designed for operation with safety extra-low voltage. This means 
that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 can 
be connected to the power supply terminals. 
The power supply unit to supply the SCALANCE X208 must comply with NEC Class 2 
(voltage range 18 - 32 V, current requirement 350 mA) 
If the device is connected to a redundant power supply (two separate power supplies), both 
must meet these requirements. 
The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low 
voltage (SELV), DC 24 V). 
Never connect the SCALANCE X208 to AC voltage or DC voltage higher than 32 V DC. 
 
Signaling Contact 
The signaling contact is connected to a 2-pin plug-in terminal block. The signaling contact 
(relay contact) is a floating switch with which error/fault states can be signaled by breaking 
the contact.  
 
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line 
Commissioning Manual, 1,   
4-11