Diagnostics over Industrial Ethernet 
 
6.2 Web Based Management (WBM) 
 
Figure 6-17  "Agent Configuration" Dialog 
IP Address Text Box 
The IP address of the SCALANCE X-200. If you make a change here, the WBM loses the 
connection to the SCALANCE X-200. Enter the new address in the Internet browser to 
reestablish the connection. 
Subnet Mask Text Box 
Here, you enter the subnet mask of the SCALANCE X-200. 
Default Gateway Text Box 
If the PC with the Internet browser is not in the same subnet as the SCALANCE X-200, you 
must enter the IP address of the default gateway here. 
6.2.4.13  The "Agent Event Configuration" WBM Menu 
Agent Event Configuration 
On this page, you specify how the SCALANCE X-200 reacts to system events. By selecting 
the corresponding check box, you specify how the SCALANCE X-200 reacts to the various 
events The following options are available: 
•  The SCALANCE X-200 sends an E-mail. 
•  The SCALANCE X-200 triggers an SNMP trap. 
 
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line 
Commissioning Manual, 1,   
6-21