11. Storage
__________________________________________________________
____
10.1 Storage conditions
Store the UPS covered and upright in a cool , dry location, with its battery fully
charged. Before storing, charger the UPS for at least 4 hours. Remove any
accessories in the accessory slot and disconnect any cables connected to the
computer interface port to avoid unnecessary draining the battery.
10.2 Extended storage
During extended storage in environments where the ambient temperature is -15
to +30 ℃ (+5 to +86 ℉), charge the UPS‘s battery every 6 months.
During extended storage in environments where the ambient temperature is
+30 to +45 ℃ (+86 to +113 ℉), charge the UPS‘s battery every 3 months.
12. Specifications
__________________________________________________________
____
MODEL
325A
425A(P)
525A(P)
625A(P)
Capacity
325VA
425VA
525VA
625VA
Voltage
100V, 110V, 120V, 220V, 232V, 240V, +/-25%
INPUT
Frequency
50 or 60Hz +/-5% (auto sensing)
Voltage
(on battery)
Simulated sine wave at Line Input +/-5%
Frequency
(on battery)
50 or 60Hz +/-0.5%
Voltage
Regulation
AVR
AVR automatically increase output voltage 15% above input
voltage if -9% to-25% of nominal. AVR decrease output voltage
13% below input voltage if+9% to 25% of nominal
OUTPUT
Transfer Time
2/4 milliseconds, including detection time
Spike Protection
320 joules, 2ms
EMI/RFI filter
10dB at15MHz, 50dB at 30MHz
(for xxxAP models only)
Overload
Protection
UPS automatic shutdown if overload exceeds 110% of nominal at
60 second and 130% at 3 seconds.
Unit Input
Fuse for overload & short circuit protection
10Baase-T
Cable Port
Network (UTP, RJ-45) compatible jacks
(for xxxAp models only)
PROTECTION
and
FILTERING
Short Circuit
UPS output cut off immediately or input fuse protection
BATTERY
Type
Sealed, maintenance-free lead acid