Two-stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the 
inverter changes the rate of acceleration and 
deceleration from the initial settings (F_02 
and F_03) to use the second set of accelera-
tion/deceleration values. When the terminal is 
turned OFF, the inverter is returned to the 
original acceleration and deceleration time 
(F_02 acceleration time 1, and F_03 decelera-
tion time 1). Use A_92 (acceleration time 2) 
and A_93 (deceleration time 2) to set the 
second stage acceleration and deceleration 
times.
In the graph shown above, the [2CH] becomes active during the initial acceleration. This 
causes the inverter to switch from using acceleration 1 (F_02) to acceleration 2 (A_92).
Output
frequency
[FW], 
[RV]
[2CH]
t
target
frequency
second
initial
1
0
1
0
Option
Code
Terminal 
Symbol
Function Name
Input 
State
Description
09
2CH
2-stage Acceleration 
and Deceleration
ON
Frequency output uses 2nd-stage acceleration 
and deceleration values
OFF
Frequency output uses the initial acceleration 1 
and deceleration 1 values
Valid for inputs:
C_01, C_02, C_03, C_04, 
C_05
Required settings:
A_92, A_93, A_94=00
Notes:
Function A_94 selects the method for second stage 
acceleration. It must be set = 00 to select the input 
terminal method in order for the [2CH] terminal 
assignment to operate.
Example (requires input configuration—
see page 
):
See I/O specs on page 
1
2
3
4
5
L
P24
2CH